| Ethernet I/O Module with 8-ch universal AI, 4-ch DO |
|
| |
| ~ Phased out ~ |
|
 |
 |
Model: ET-7019 |
Model: PET-7019 |
|
|
 |
- Built-in Web Server
- Web HMI
- Support for both Modbus TCP and Modbus UDP Protocols
- Communication Security
- Dual Watchdog
- Wide Operating Temperature Range: -25 ~ +75°C
- I/O Pair Connection
- Built-in I/O
- AI: 8 Channels with 240 Vrms Overvoltage Protection
- DO: 4 Channels
|
|
|
| |
 |
The ET-7019/PET-7019 features an extremely excellent protection mechanism where overvoltage protection is up to 240 Vrms. It has wider input range for voltage compared to ET-7017. ET-7019/PET-7019 measures voltage from +/-15 mV ~ +/-10 V. Its input type also includes current and thermocouple. An intuitive design is built in this model, measuring current or voltage simply by a jumper. An external resistor is no longer needed. Eight of its inputs channels can individually be configured with different kinds of analog input. Moreover, the ET-7019/PET-7019 also got open thermocouple detection and many protection mechanisms. The 4 digital output can be set as alarm output with Short-circuit protection and overload protection. |
| |
 |
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment. |
| |
 |
| Models |
ET-7019 |
PET-7019 |
| Software |
| Built-In Web Server |
Yes |
| Web HMI |
Yes |
| I/O Pair Connection |
Yes |
| Communication |
| Ethernet Port |
10/100 Base-TX with Auto MDI/MDI-X |
| PoE |
- |
Yes |
| Protocol |
Modbus TCP, Modbus UDP |
| Security |
ID, Password and IP Filter |
| Dual Watchdog |
Yes, Module (0.8 seconds), Communication (Programmable) |
| LED Indicators |
| L1 (System Running) |
Yes |
| L2 (Ethernet Link/Act) |
Yes |
| L3 (Ethernet 10/100 M Speed) |
Yes |
| PoE Power |
- |
Yes |
| 2 Way Isolation |
| Ethernet |
1500 VDC |
- |
| I/O |
2500 VDC |
2500 VDC |
| EMS Protection |
| ESD (IEC 61000-4-2) |
4 kV Contact for Each Terminal and 8 kV Air for Random Point |
| EFT (IEC 61000-4-4) |
+/-4 kV for Power |
| Power |
| Reverse Polarity Protection |
Yes |
| Powered from Terminal Block |
Yes, 10 ~ 30 VDC |
Yes, 12 ~ 48 VDC |
| Powered from PoE |
- |
Yes, IEEE 802.3af, Class1 |
| Power Output |
- |
- |
| Consumption |
2.6 W (Max.) |
2.9 W (Max.) |
| Mechanical |
| Dimensions (W x L x H) |
72 mm x 123 mm x 35 mm |
| Installation |
DIN-Rail or Wall mounting |
| Environmental |
| Operating Temperature |
-25 ~ +75 °C |
| Storage Temperature |
-30~ +80 °C |
| Humidity |
10 ~ 90% RH, non-condensing |
|
| |
 |
| Analog Input |
| Channels |
8 (Differential) |
| Sensor Type |
+/-15 mV, +/-50 mV, +/-100 mV, +/-150 mV, +/-500 mV, +/-1 V, +/-5 V, +/-10 V, +/-20 mA, 0~20 mA, 4~20 mA |
| Thermocouple (J, K, T, E, R, S, B, N, C, L, M, , and LDIN43710) |
| Strain Gauge Type |
Full-Bridge, Half-Bridge, and Quarter-Bridge |
| Individual Channel Configuration |
Yes |
| Resolution |
16-bit |
| Sampling Rate |
10 samples/Second total |
| Accuracy |
+/-0.1 % or better |
| Zero Drift |
+/-10 μV/°C |
| Span Drift |
+/-25 ppm/°C |
| Overvoltage Protection |
240 Vrms |
| Input Impedance |
Voltage |
>1 MΩ |
| Current |
125 Ω |
| Common Mode Rejection |
86 dB Min. |
| Normal Mode Rejection |
100 dB |
| Temperature Output Consistency |
No |
| Stable Temperature Output in the Field |
No |
| Open Wire Detection |
Yes |
| Virtual Channel to Channel Isolation |
+/-400 VDC |
| Digital Output |
| Channels |
4 |
| Type |
Isolated Open Collector |
| Sink/Source (NPN/PNP) |
Sink |
| Max. Load Current |
700 mA/Channel |
| Load Voltage |
5 VDC ~ 50 VDC |
| Overvoltage Protection |
60 VDC |
| Overload Protection |
1.4 A |
| Short-circuit Protection |
Yes |
| Power-on Value |
Yes, Programmable |
| Safe Value |
Yes, Programmable |
| Note: For highly-accurate thermocouple measurement, ICP DAS recommends selecting the ET-7018Z/ET-7019Z module,which features automatic cold-junction compensation for each channel, ensuring consistent and stable temperature output. |
|
| |
 |
ET-7019 CR |
Ethernet I/O Module with 8-ch universal AI, 4-ch DO (RoHS) |
PET-7019 CR |
PoE Ethernet I/O Module with 8-ch universal AI, 4-ch DO (RoHS) |
|
| |
 |
| NS-205 CR |
Unmanaged 5-port Industrial Ethernet Switch; reguires 24 VDC Input (RoHS) |
| NS-205PSE CR |
Unmanaged Ethernet switch with 4-PoE and 1 RJ45 uplink; reguires 48 VDC Input (RoHS) |