tM-7530

Tiny RS-232/CAN converter
tM-7530
tM-7530
tM-7530
tM-7530
tM-7530
tM-7530

Features

  • Compatible with CAN specification 2.0A and 2.0B
  • Fully compatible with ISO 11898-2 standard
  • Support various CAN baud rate from 10K bps to 1M bps
  • Support user-defined CAN baud rate
  • Support various RS-232 baud rate from 110 bps to 230400 bps
  • External option 120 Ω terminal resistor
  • Software configurable CAN and RS-232 communication parameters
  • Power, data flow and error indicator for CAN and RS-232
  • Watchdog inside
  • Support pair connection mode
  • Software buffer on CAN bus side and RS-232 side
  • Support user-defined end of characters on pair connection mode
  • Support listen only mode
  • Support time stamp response on RS-232 side
CE UKCA FCC RoHS WEEE

Introduction

ICP DAS has provided a lot of UART/CAN product solutions which are widely recommended in the market. These UART/CAN converters can help users to implement the communication between RS-232 and CAN network. In order to cater for costing requirement, we provide a new solution of RS-232/CAN converter-tM-7530. The tM-7530 is a tiny RS-232/CAN to fit narrower environment as a result of its small size. It has isolation on power side and on CAN bus side and its performance is faster than other RS-232/CAN module. The function of tM-7530 can full compatibly with I-7530 and I-7530T. Besides, it provides new function such as listen only. User can use this function to listen CAN bus messages and error detection. According to above features, tM-7530 is an economical and practical RS-232/CAN converter solution.

Moreover, we expand the functionalities of tM-7530 for some special application. In pair connection mode, tM-7530 can be used to connect PC with other RS-232 devices at the same time. The application architecture may be as follows.


Applications

  • Control System
  • Building Automation
  • Factory Automation
  • Distributed data acquisition

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES tM-7530     CR DESCRIPTIONIntelligent tiny RS-232/CAN converter (RoHS)
This combination include other products.

Similar Products

LED Indicators
Status 1 x Run LED: Power and Data Flow
1 x Err LED: Error
COM Ports
Ports 1 x RS-232
(9-pin female D-Sub (TxD, RxD, GND))
Baud Rate 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200, 230400 bps
Parity None, Even, Odd
Data Bit 5, 6, 7, 8
Stop Bit 1, 2
CAN
Ports 1
Baud Rate 10 k ~ 1 M bps
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
Terminal Resistor External option terminal resistor
Specification ISO-11898-2, CAN 2.0A and CAN 2.0B
Filter Yes
Power
Input Range +10 VDC ~ +30 VDC
Consumption 1 W
Mechanical
Casing Plastic
Dimensions (mm) 52 x 86 x 32 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing

The tM-7530 uses VxCAN Utility to configure and test. VxCAN is a technique of ICP DAS and we call it "Virtual CAN". It is used to integrate all of ICP DAS CAN converter modules. Via this technique and its Windows platform API, users can develop utility tool by themselves to fit their application. The VxCAN Utility is also developed by using this method. Thus, we will integrate all CAN converter utility via VxCAN Utility in the future. About more VxCAN information, please refer to VxCAN Utility website.


Software Utility Features 

  • CAN bus baud rate configuration
  • CAN bus acceptance filter configuration
  • CAN 2.0A or CAN 2.0B specific selection
  • RS-232 baud rate and data format configuration
  • Communication mode(normal , pair connection , and listen only mode ) configuration
  • Easy test to transmit/receive CAN messages
  • CAN bus data flow detection
  • Group Send CAN messages for special application
  • Trigger event setting for advance received CAN messages
  • Integrate all CAN bus converter utility of ICP DAS

Performance Test

Performance test: from CAN to RS-232(115200, n, 8, 1). Unit: Frames Per Second(FPS).
Baud rate 1000K 800K 500K 250K 125K 50K 20K 10K
CAN 2.0A 519 519 523 522 522 416 176 88
CAN 2.0B 423 423 426 425 426 353 146 74
 
Performance test: from RS-232(115200, n, 8, 1) to CAN. Unit: Frames Per Second(FPS).
Baud rate 1000K 800K 500K 250K 125K 50K 20K 10K
CAN 2.0A 523 524 523 522 520 451 180 90
CAN 2.0B 425 426 427 426 427 377 150 75