iSN-301V/DIN

1-ch Rangefinder Module
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN
iSN-301V/DIN

Features

  • Non-contact Distance Measurement (Time-of-Filght)
  • Distance Measurement: 5 cm ~ 4 m
  • Typical Full Field-of-View (FoV): 27°
  • Programmable Region-of-Interest (ROI) Size and Position
  • Supports the DCON and the Modbus RTU Protocols
CE UKCA RoHS WEEE

Introduction

The iSN-301 is a Time-of-Flight sensing module that is designed specifically for non-contact distance measurement. It can measure distance up to 4 meters. The module can be configured to trigger LED alarm when the distance is too short or too long. It is possible to program the size and position of the ROI to adjust the sensor FoV. The module can be easily integrated with the host controller connected in the same RS-485 network via DCON or Modbus RTU protocol.

Applications

  • Lighting and exhaust fans in toilets and restrooms
  • Common lighting in staircases
  • Lighting in parking areas
  • Garden lighting
  • Lighting for changing rooms in shops
  • Corridor lighting, and many more situations
  • Sanitary (robust user detection whatever the target reflectance)
  • Smart building (people detection)








 

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES iSN-301V/DIN     CR DESCRIPTION1-ch Rangefinder Module (Vertical) (DIN Rail mount) (RoHS)
This combination include other products.

Similar Products

EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power
ESD (IEC 61000-4-2) ±8 kV Air for Random Point
LED Indicators
Status 1 as Power Indicator. 1 as Alarm Indicator.
Distance Measurement
Detection Range 5 cm ~ 4 m
Detection Field of View 15°; Diameter 0.8 meters Max.
Accuracy ±5% (±20 cm)
Resolution 1 mm
Update Time 20 ~5000 ms, programmable
Sensor Direction Vertical
Relay Output
Type Signal Relay, Form A x1, SPST
0.25 A @ 250 VAC
0.5 A @ 125 VAC
2 A @ 30 VDC
COM Ports
Ports 1 x RS-485
Baud Rate Software Configurable: 1200 ~ 115200 bps
Data Format N,8,1 / O,8,1 / E,8,1 / N,8,2
Protocol Modbus RTU or DCON
Node Address 0 ~ 255 for software configuration
96 ~ 127 for hardware configuration
Power
Reverse Polarity Protection Yes
Input Range 10 ~ 30 VDC
Consumption 1.2 W Max.
Mechanical
Dimensions (mm) 52 x 84 x 27 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +80°C
Humidity 10 ~ 90% RH, Non-condensing