ZT-2015

ZigBee Wireless 6-ch RTD Input Module with 3-wire RTD Lead Resistance Elimination (ZigBee Router) (Asia Only)
ZT-2015
ZT-2015
ZT-2015
ZT-2015
ZT-2015
ZT-2015
ZT-2015
ZT-2015
ZT-2015
ZT-2015

Features

  • ISM 2.4 GHz Operating Frequency
  • Fully Compliant with 2.4 G / ZigBee Specifications
  • Wireless Transmission Range up to 700 m
  • External DIP and Rotary Switches for easy Configuration
  • GUI Configuration Software (Windows Version)
  • 3-wire RTD Input with Lead Resistance Elimination
  • Individual Channel Configuration
  • Open Wire Detection
  • Overvoltage Protection
  • DIN-Rail Mounting
FCC RoHS WEEE

Introduction

The ZT-2015 offers 6 wireless input channels, each of which can be connected to different kinds of RTD sensors. It features automatic compensation for 3-wire RTD, with long-distance measurement capabilities so that it can measure accurately regardless of the length of the wires. Also the ZT-2015 is fully RoHS-compliant and has qualification for 4 kV ESD protection as well as 3000 VDC intra-module isolation. Users can easily configure the module address, protocol, checksum, ZB-PID, ZB-channel and type code settings using a combination of rotary and DIP switches.

Applications

Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
ZT-2015

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES ZT-2015     CR DESCRIPTIONZigBee Wireless 6-ch RTD Input Module with 3-wire RTD Lead Resistance Elimination (ZigBee Router) (RoHS) (Asia Only)
This combination include other products.

Similar Products

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Isolation
Intra-module Isolation 3000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for Power Line, Communication Line and each Channel,
±8 kV Air for Random Point
Surge (IEC 61000-4-5) ±3 kV for Power Line
LED Indicators
Status 1 x Power and Communication
ZigBee
Antenna 2.4 GHz - 5 dBi Omni directional
Certifications FCC/FCC ID, CE (RED excluded)
Max. Slaves 255
Protocol Supports DCON and Modbus RTU Protocols
Standard 11 dBm (FCC Certificated) (Max. 19 dBm)
Transmission Power 11 dBm (FCC Certificated) (Max. 19 dBm)
Transmission Distance (LoS) 700 m (Typical)
Analog Input
Channels 6
Type 2/3-wire RTD
Sensor Type Pt100, Pt1000, Ni120, Cu100, Cu1000
Sampling Rate 12 Samples/Sec. (Total)
Common Mode Rejection 150 dB
Normal Mode Rejection 100 dB
Overvoltage Protection 120 VDC/110 VAC
Individual Channel Configuration Yes
Open Wire Detection Yes
3-wire RTD Lead Resistance Elimination Yes
Analog Output
Accuracy ±0.05%
Power
Input Range +10 VDC ~ +30 VDC
Consumption 1.5 W Max.
Mechanical
Dimensions (mm) 33 x 87 x 110 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -30 ~ +80°C
Humidity 10 ~ 90% RH, Non-condensing