RPS-4M/W2

4-slot Industrial Redundant Power Supply. Includes two RPS-100 modules
RPS-4M/W2
RPS-4M/W2
RPS-4M/W2
RPS-4M/W2
RPS-4M/W2
RPS-4M/W2

Features

  • Max 400W output power, each slot can insert a 100W power module
  • N+1 Redundant, maximum N=3
  • Power module supports hot swapping
  • Detect current load of module
  • Detect temperature of module
  • Easy installation.
  • Support Modbus RTU/TCP Protocol
CE UKCA FCC RoHS WEEE

Introduction

The RPS series redundant power supply uses N+1 parallel current sharing (with Load Balancing) method to achieve power backup and stable power supply, and supports hot swapping design. The RPS series provides communication functions (supports Modbus RTU/TCP) for real-time monitoring, reducing inspection manpower.

  • Each slot can plug in a 100W power module
  • 4-slot design for N+1 redundancy
    • The RPS can provide rated power of 3 power modules (300W) when 4 power modules are inserted.
    • The RPS can still supply power at all times when any power module fails. (Number of inserted modules > 1)
  • Built-in Load Balancing
    The load current will be evenly distributed to each power module to avoid premature failure of one power module due to overuse.
  • The power module supports hot swapping
  • Built-in power module diagnostic function
    • Temperature
    • Output current
    • Module failure (with one relay output)
    • Usage time
  • Support Modbus RTU/TCP protocol
    Diagnostic information can be access via RS-485, Ethernet

Applications

The RPS series can be used with ICP DAS’s redundant solutions, including I/O redundancy (data acquisition), controller redundancy (program control), ethernet ring communication redundancy (ring network communication) and HMI redundancy (display information record) to form a complete redundant system.

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES RPS-4M/W2     CR DESCRIPTION4-slot Industrial Redundant Power Supply. Includes two RPS-100 modules (RoHs)
This combination include other products.

Similar Products

EMC
Standard IEC 61000-4-2(ESD): ±4 kV for Contact
IEC 61000-4-4(EFT): ±500 V for Signal
LED Indicators
Status 3, PWR, Rx, STA
Ethernet
Ports 1 x RJ-45, 10/100Base-TX
Access Control Password and IP Filter
Protocol Modbus TCP server, Web server
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
default: 9600 bps
Data Format (N,8,1),(N,8,2),(E,8,1),(O,8,1)
default:(N,8,1)
Protocol Modbus RTU slave
Node Address Hardware: 1 ~ 64
Software: 1~255
General
Slot 4, for power modules
Self-diagnostic
Current Measurement 0A~5A; +/- 0.25A
Temperature Measurement 0℃~100℃; +/- 5℃
Alarm Output 1x Relay; Form A, 5A
Power
Input Range 90 ~ 264 VAC
Consumption 110 VAC, 45 mA, 4.95W
Mechanical
Casing metal
Dimensions (mm) 133 x 266 x 177 (W x L x D)
Installation DIN-Rail
Environment
Operating Temperature -20 ~ +50 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing
  Traditional power supply IRPS-4M
Damaged Replacement Replace after power outage Affect system operation Hot swapping
Rated Power Fixed As needed
Load Balancing X V
Communication X Modbus TCP/RTU
Monitor X Current, temperature