PM-3133i-100P-EIP

Isolated 3-phase Smart Power Meter
PM-3133i-100P-EIP
PM-3133i-100P-EIP
PM-3133i-100P-EIP
PM-3133i-100P-EIP
PM-3133i-100P-EIP
PM-3133i-100P-EIP
PM-3133i-100P-EIP
PM-3133i-100P-EIP

Features

• Bi-directional Energy
• True RMS Power Measurements
• Energy Analysis for 3P4W, 3P3W, 1P3W, 1P2W
• Current Measurements Up to 60 A with Different CT Ratio
• Isolated Voltage Measurements Up to 600 V
• Clip-on CT for Easy Installation
• W Accuracy Better than 0.5% (PF=1)
• Total Harmonic Distortion (THD)
• Supports EtherNet/IP Protocol
CE UKCA FCC RoHS WEEE

Introduction

ICP DAS brings the most powerful, cost-effective, advanced Smart Power Meters PM-3133i series that gives you access to real-time electric usage for three-phase power measurement. With its high accuracy (<0.5%, PF=1 ), the PM-3133i series can be applied to both low voltage primary side and/or medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation. These compact size and cost-effective power meters are equipped with revolutionary wired clip-on CT (various types, support input current up to 400 A). It operates over a wide input voltages range 10 ~ 600 VAC which allows worldwide compatibility. Built-in AC isolator protection, this means total isolation between the AC measurement side and the control side.

Applications


• Generator monitoring
• Switchgear distribution systems
• Energy Management
• Power quality analysis

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES PM-3133i-100P-EIP     CR DESCRIPTIONEtherNet/IP, Isolated 3-phase power meter; includes 60A CT (Inside diameter 10 mm; wire lead 4 m) x 3 (RoHS)
This combination include other products.

Similar Products

AC Power Measurement
Wiring 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Loops Three-phase
Input Voltage 10 ~ 600 V
Input Current CTØ10 mm (0.05 A ~ 60 A)
Input Frequency 50/60 Hz
W Accuracy Better than 0.5% (PF=1)
Power Parameter Measurement True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency
Data Update Rate 1 Second
CT
Includes CTs 3
Type Clip
Max. Current 60 A
Inside Diameter 10 mm
Leading Cable 4 m
COM Ports
Protocol EtherNet/IP
Power
Input Range +12 ~ 48 VDC
Consumption 2 W
Alarm Output Form A (Normal Open) x 2; Relay Contact Voltage Range: 5 A @ 250 VAC (47 ~ 63 Hz), 5 A @ 30 VDC
Mechanical
Casing Plastic
Dimensions (mm) 33 x 127 x 100 (W x L x H)
Installation DIN-Rail Mounting
Environment
Operating Temperature -20 ~ +70 °C
Storage Temperature -25 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing