PM-2133D-100P-MTCP

3-phase Smart Power Meter with LED Display

Features

• Bi-directional Energy
• True RMS Power Measurements
• Energy Analysis for 3P4W, 3P3W, 1P3W, 1P2W
• Current Measurements Up to 60 A with Different CT Ratio
• Voltage Measurements Up to 500 V
• Clip-on CT for Easy Installation
• W Accuracy Better than 0.5% (PF=1)
• Total Harmonic Distortion (THD)
• 8-Digit LED Display
• Supports Modbus TCP Protocol
 
CE UKCA FCC RoHS WEEE

Introduction

ICP DAS brings the most powerful, cost-effective, advanced Smart Power Meters PM-2133D series that gives you access to real-time electric usage for three-phase power measurement. With its high accuracy (<0.5%, PF=1 ), the PM-2133D series can be applied to both low voltage primary side and/or medium/high voltage secondary side and enables the users to obtain reliable and accurate energy consumption readings from the monitored equipments in real time under operation. These compact size and cost-effective power meters are equipped with revolutionary wired clip-on CT (various types, support input current up to 400 A). It operates over a wide input voltages range 10 ~ 500 VAC which allows worldwide compatibility. This meter has LED display shows power.

Applications


• Generator monitoring
• Switchgear distribution systems
• Energy Management
• Power quality analysis

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES PM-2133D-100P-MTCP     CR DESCRIPTIONModbus TCP, 3-phase power meter; includes 60A CT (Inside diameter 10 mm; wire lead 4 m) x 3 (RoHS)
This combination include other products.

Similar Products

AC Power Measurement
Wiring 3P4W-3CT, 3P3W-2CT, 3P3W-3CT, 1P2W-1CT, 1P3W-2CT
Loops Three-phase
Input Voltage 10 ~ 500 V
Input Current CTØ10 mm (0.05 A ~ 60 A)
Input Frequency 50 Hz (Range 45 ~ 55 Hz)/60 Hz (Range 55 ~ 65 Hz)
W Accuracy Better than 0.5% (PF=1)
Power Parameter Measurement True RMS voltage (Vrms), True RMS current (Irms), Active Power (kW), Active Energy (kWh), Apparent Power (kVA), Apparent Energy (kVAh), Reactive Power (kVAR), Reactive Energy (kVARh), Power Factor (PF), Frequency (45 ~ 65 Hz)
Data Update Rate 1 Second
LED Display Yes, 8-digit
CT
Includes CTs 3
Type Clip
Max. Current 60 A
Inside Diameter 10 mm
Leading Cable 4 m
Ethernet
Protocol Modbus TCP
Power
Input Range +85 ~ +264 VAC (277 VAC available)
Consumption 6 W
Mechanical
Casing Plastic
Dimensions (mm) 110 x 115 x 50 (W x L x H)
Installation Panel Mounting
Environment
Operating Temperature -20 ~ +70 °C
Storage Temperature -25 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing