M-7016-G
Introduction
In the industrial environment, there are numerous examples where force needs to be converted into measurable electrical output. In most cases, a strain gauge or a load cell can be used. But the question is, how do we then deal with these electrical output measurements? In this situation, The M-7016 is definitely the No. 1 choice. Not only can the module process data from a load cell or a strain gauge, but it also features linear mapping that can be used to directly convert the resulting data into weight via a user-defined correspondent table.
The M-7016 supports full-bridge strain gauges and provides 2 analog input channels, 1 excitation voltage output channel, 1 digital input channel, and 4 digital output channels. The module provides a programmable input range (±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, and ±2.5 V) and each analog input channel can be individually configured. The excitation voltage output can be in the range of 0 ~ +10 V, with a 40 mA driving efficiency. Digital output channels can also be set as high or low alarm outputs. The M-7016 supports Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7016.
The M-7016 supports full-bridge strain gauges and provides 2 analog input channels, 1 excitation voltage output channel, 1 digital input channel, and 4 digital output channels. The module provides a programmable input range (±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, and ±2.5 V) and each analog input channel can be individually configured. The excitation voltage output can be in the range of 0 ~ +10 V, with a 40 mA driving efficiency. Digital output channels can also be set as high or low alarm outputs. The M-7016 supports Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7016.
Applications
• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment
Ordering Information
PRODUCT SERIES | DESCRIPTION | QNT. | INQUIRY |
---|---|---|---|
This combination include other products.
Similar Products
CPU Module | |
---|---|
Watchdog Timer | Module, Communication (Programmable) |
Isolation | |
---|---|
Intra-module Isolation | 1500 VDC |
EMS Protection | |
---|---|
EFT (IEC 61000-4-4) | ±4 kV for Power Line |
ESD (IEC 61000-4-2) | ±4 kV Contact for Each Terminal ±8 kV Air for Random Point |
LED Indicators | |
---|---|
Status | 1 x Power and Communication |
Digital Input/Counter | |
---|---|
Channels | 1 |
Type | Dry Contact |
Sink/Source (NPN/PNP) | Source |
ON Voltage Level | Close to GND |
OFF Voltage Level | Open |
Max. Counts | 65535 (16-bit) |
Frequency | 50 Hz |
Input Impedance | 3 kΩ |
Overvoltage Protection | ±30 VDC |
Digital Output | |
---|---|
Channels | 4 |
Type | Open Collector |
Sink/Source (NPN/PNP) | Sink |
Load Voltage | +3.5 ~ +50 VDC |
Load Current | 30 mA/Channel |
Power on Value | Programmable |
Safe Value | Programmable |
Strain Gauge, Load Cell Input | |
---|---|
Channels | 2 |
Type | Full-Bridge Strain Gauge Voltage Current |
Range | Voltage: ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V Current: ±20 mA |
Wiring | 4-wire |
Accuracy | ±0.05% of FSR |
Resolution | 16-bit |
Sampling Rate | 1-ch Mode: 10 Hz 2-ch Mode: 2 Hz (total) |
Impedance | 20 MΩ |
Overvoltage Protection | ±5 VDC |
Excitation Voltage Output | |
---|---|
Channels | 1 |
Range | 0 ~ +10 V |
Resolution | 16-bit |
Accuracy | ±0.05% of FSR |
Max. Load Current | 40 mA |
Power on Value | Programmable |
COM Ports | |
---|---|
Ports | 1 x RS-485 |
Baud Rate | 1200 ~ 115200 bps |
Data Format | (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1) |
Protocol | Modbus RTU, DCON |
Power | |
---|---|
Reverse Polarity Protection | Yes |
Input Range | +10 ~ +30 VDC |
Consumption | 2.4 W |
Mechanical | |
---|---|
Dimensions (mm) | 72 x 123 x 35 (W x L x H) |
Installation | DIN-Rail Mounting |
Environment | |
---|---|
Operating Temperature | -25 ~ +75 °C |
Storage Temperature | -40 ~ +85 °C |
Humidity | 10 ~ 95% RH, Non-condensing |