Features


• Strain Gauge Measurement
• High Resolution: 16-bit
• Excitation Voltage Output : 0 ~ 10 V
• Individual Channel Configuration
• 2-channel Digital Inputs
• 2-channel Digital Outputs
CE FCC RoHS WEEE

Introduction

Around our surroundings, there are numerous examples of converting force into a measurable electrical output; In most cases, we need a strain gauge or a load cell. But the question is that how do we deal with these electrical outputs? I-87016W is definitely your NO.1 choice! It not only processes the data from load cells or strain gauges, but also features linear mapping that generates intuitive and synchronic results for you; by user-defined corespondent table, I-87016W converts the data into weight directly!

Applications


• Industrial Automation
• Industrial Machinery
• Building Automation
• Semiconductor Fabrication
• Control Systems

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES I-87016W-G     CR DESCRIPTION2-ch Isolated Strain Gauge Input Module (RoHS)
This combination include other products.

Similar Products

CPU Module
Watchdog Timer Yes, Module (1.6 Seconds), Communication (Programmable)
Isolation
Intra-module Isolation 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ± 4 kV Contact for Each Terminal
±8 kV Air for Random Point
LED Indicators
Status 1 x Power and Communication
4 x I/O
Digital Input/Counter
Channels 2
Type Wet Contact
Sink/Source (NPN/PNP) Sink
ON Voltage Level +3.5 VDC ~ 50 VDC
OFF Voltage Level +1 VDC Max.
Frequency 50 Hz Max.
Min. Pulse Width 10 ms
Input Impedance 10 KΩ, 0.66 W
Channel-to-Channel Isolation Yes
Digital Output
Channels 2
Type Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage +3.5 VDC ~ +50 VDC
Load Current 700 mA/channel
Short-circuit Protection Yes
Power on Value Yes
Safe Value Yes
Strain Gauge, Load Cell Input
Channels 2
Range +/-15 mV, +/- 50 mV, +/-100 mV,+/-500 mV, +/-1 VDC, +/-2.5 VDC
-20 mA ~ +20 mA (No External Resistor Required)
Wiring Full-Bridge, Half-Bridge, Quarter-Bridge
Accuracy Voltage: ±0.05% of FSR
Current: ±0.1% of FSR
Resolution 16-bit
Sampling Rate 10 Hz (Total)
Impedance Voltage Input: >400 kΩ,
Current Input: 125 Ω
Individual Channel Configuration Yes
Long Distance Measurement Yes
Commond Mode Rejection 150 dB min.
Nrmal Mode Rejection 100 dB
Excitation Voltage Output
Channels 1
Range 0 ~ +10 VDC
Resolution 16-bit
Accuracy +/- 0.05% of FSR
Max. Load Current 80 mA
Output Capacity 10 VDC @ 80 mA
Drift +/- 50 ppm/°C
COM Ports
Ports 1 x RS-485
Baud Rate 1200 to 115200 bps
Data Format N, 8, 1
Protocol DCON
Power
Consumption 1.1 W Typical
2.5 W Max.
Mechanical
Dimensions (mm) 30 x 102 x 115 (W x L x H)
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing