I-7532-G

2022/11/01 supply resumed
Two-channel CAN Bus Isolated Bridge
I-7532-G
I-7532-G
I-7532-G
I-7532-G
I-7532-G
I-7532-G
I-7532-G
I-7532-G

Features

  • Fully compatible with the ISO 11898-2 standard
  • Support both CAN 2.0A and CAN 2.0B
  • Selectable 120Ω terminator resistor by jumper
  • Up to 100 CAN nodes on each channel
  • 768 data frames for each CAN channel
  • Rotary switch for CAN baud rate from 5Kbps to 1Mbps or programmable user-defined CAN baud rate
  • Support CAN bus message acceptance filter configuration
  • Support firmware update via CAN1 of I-7532
  • CAN messages can be forwarded under another identifier
  • Support CAN Bus-Off Auto-Reset function
  • Support CAN Listen-Only Mode function
CE UKCA FCC RoHS WEEE

Introduction

I-7532 is a CAN bridge that can be used to integrate two CAN networks with the different CAN baud rate. When some errors (e.g. bit error) happened on one CAN port of I-7532, the other CAN port of I-7532 will not be affected. By using I-7532, users can achieve the following application easily and suitable for any CAN protocol like CANopen, DeviceNet, J1939 etc.

(1) Extend CAN bus network distance.
(2) Connect two CAN bus networks with different baud rate.
(3) Raise the number of node in CAN bus network.
(4) Integrate multi the same CAN devices in the CAN network.

Applications

  • Control System
  • Building Automation
  • Factory Automation
  • Distributed data acquisition

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES I-7532-G     CR DESCRIPTIONTwo-channel CAN Bus Isolated Bridge (RoHS)
This combination include other products.

Similar Products

CAN
Ports 2
Baud Rate 5 k ~ 1 M bps
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
Terminal Resistor Jumper for 120 Ω terminal resistor
Specification ISO-11898-2, CAN 2.0A and CAN 2.0B
Filter Yes
Time Delay [ 1Mbps (8-byte Data) ] ID-29bit => 156 us ; ID-11bit => 134 us
[ 5Kbps (8-byte Data) ] ID-29bit => 30 ms ; ID-11bit => 25 ms
Power
Input Range +10 VDC ~ +30 VDC
Consumption 2 W
Mechanical
Casing Plastic
Dimensions (mm) 72 x 122 x 33 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
  • Provide CAN bus User-Defined Baud Rate / CAN-ID Acceptance Filter / CAN-ID Mapping configuration
  • Provide saving the CAN acceptance filter data to file. The “*.dat” file format is compatible with configuration file of I-7565-H1/H2. The “*.xls” file is useful for CAN hardware interface of other companies to configure CAN-ID filter function of I-7532
  • Support ICP DAS CAN hardware interface including “RS232 to CAN”, “Ethernet to CAN”, “USB to CAN”, “CAN Card” series products for configuration

Baud Rate Selection by Rotary Switch

Switch Value 0 1 2 3
Baud [bps] Config
Mode
5k or User-defined
CAN baud
10k 20k
Switch Value 4 5 6 7
Baud [bps] 40k 50k 80k 100k
Switch Value 8 9 A B
Baud [bps] 125k 200k 250k 400k
Switch Value C D E F
Baud [bps] 500k 600k 800k 1000k