I-7530A-G

RS-232/422/485 to CAN Converter
I-7530A-G
I-7530A-G
I-7530A-G
I-7530A-G

Features

  • Compatible with CAN specification 2.0A and B
  • Fully compatible with ISO 11898-2 standard
  • Jumper for 120 Ω terminal resistor
  • Software configurable CAN and RS-232 /422/485 communication parameters
  • Power, data flow and error indicator for CAN and RS-232/422/485
  • Watchdog inside
  • Provide the transparent communication between the RS-232/485/422 devices via CAN bus
  • Enable different RS-232/485/422 devices into an individual group in CAN bus network
    (Full-duplex communication mode of RS-232/422 devices is not supported)
  • 3 kV galvanic isolation
  • 2500 Vrms photocoupler isolation on the CAN side
CE UKCA FCC RoHS WEEE

Introduction

The I-7530A is an RS-232/422/485 to CAN converter. It is a member of the I-7530 serial family, and inherits all of the features of the I-7530. The CAN interface of the I-7530A follows ISO 11898-2 specifi cation, the maximum CAN baud is up to 1 Mbps. There is one COM port in the I-7530A. As the I-7530A runs, it only receives the commands from one of these COM interfaces (i.e. from the RS-232, RS-485 or RS-422 interface) at the same time, but the CAN messages will be forwarded to all of these COM interfaces.

Moreover, we expand the functionalities of I-7530A for some special application. In pair connection mode, I-7530A can be used to connect PC with other RS-232/485/422 devices at the same time. The application architecture may be as follows.

3000V isolation on CAN side
The CAN port of I-7530A is an isolated with 3000V isolation. This isolation can protect the local RS-232/485/422 devices from the damage signal coming from CAN network.

Watchdog inside
The I-7530A Watchdog is a hardware reset circuit to monitor the I-7530A’s operation status. When working in harsh or noisy environment, the I-7530A may be down by the external signal. The circuit may let the I-7530A to work continuously and never halt.

Power and Error indicator display
There are two indicators on the I-7530A.The power indicator can help user to check whether the I-7530A is standby or transmitting/receiving messages. The Error indicator will be turned on when some errors occur on the I-7530A.  

Applications

  • Control System
  • Building Automation
  • Factory Automation
  • Distributed data acquisition

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES I-7530A-G     CR DESCRIPTIONIntelligent RS-232/485/422 to CAN converter (RoHS)
This combination include other products.

Similar Products

LED Indicators
Status 1 x Power
1 x CAN status
COM Ports
Ports 1 x RS-232
1 x RS-485 (self-tunner ASIC inside)
1 x RS-422 (self-tunner ASIC inside)
(these ports can’t be used simultaneously)
Baud Rate 110, 150, 300, 600, 1200, 2400, 4800, 9600, 19200, 38400, 57600, 115200 bps
Parity None, Even, Odd
Data Bit 5, 6, 7, 8
Stop Bit 1,2
Receive Buffer 900 data frames
CAN
Ports 1
Baud Rate 10 k ~ 1 M bps
Isolation 3000 VDC for DC-to-DC, 2500 Vrms for photo-couple
Terminal Resistor Selectable 120Ω terminal resistor by jumper
Specification CAN 2.0A/2.0B
Filter Yes
Receive Buffer 1000 data frames
Power
Input Range +10 VDC ~ +30 VDC
Consumption 1 W
Mechanical
Casing Plastic
Dimensions (mm) 72 x 118 x 33 (W x L x H)
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +80 °C
Humidity 10 ~ 90% RH, Non-condensing
  • It has a CAN message field which can display the receiving CAN messages in Decimal or HEX mode
  • Can display the timestamp of each received CAN message
  • Users can change the display mode, up-down, down-up or stop
  • It can count the number of received CAN messages
  • Data Log : It can save the CAN message as “ txt ” file
  • Has CAN ID filter function
  • Can send CAN message to CAN BUS according the defined interval time

Software Download

Software Utility Features 

  • CAN bus Baud rate configuration
  • CAN acceptance filter configuration
  • CAN 2.0A or 2.0B specific selection
  • RS-232/485/422 Baud rate and data bit setting
  • RS-232/485/422 responded selection
  • Easy test to transmit/receive CAN messages
  • Setting for I-7530A communication mode (normal mode or pair connection mode) 

Performance Test

The test is the performance which transfer 8 bytes data frame from CAN to RS232.
CAN setting Transfer frames Transfer time(ms) RS-232 setting Receive frames Receive time (ms) The max frames/sec Data<8 byes/frme RS232 command length
2.0A 1Mbps 1,000 200 115200,n,8,1 1,000 2954 338 >=338 22 B
2.0A 1Mbps 1,000 200 115200,n,7,1 1,000 2775 360 >=360 22 B
2.0B 1Mbps 1,000 200 115200,n,8,1 1,000 3580 279 >=279 27 B
2.0B 1Mbps 1,000 200 115200,n,7,1 1,000 3337 299 >=299 27 B
 
The test is the performance which transfer 8 bytes data frame from RS232 to CAN.
CAN setting Transfer frames Transfer time(ms) RS-232 setting Receive frames Receive time (ms) The max frames/sec Data<8 byes/frme RS232 command length
2.0A 1Mbps 1,000,000 2,612,243 115200,n,8,1 1,000,000 2,612,243 382 >=382 22 B
2.0A 1Mbps 1,000,000 2,441,130 115200,n,7,1 1,000,000 2,441,130 409 >=409 22 B
2.0B 1Mbps 1,000,000 3,142,043 115200,n,8,1 1,000,000 3,142,043 318 >=318 27 B
2.0B 1Mbps 1,000,000 3,142,043 115200,n,7,1 1,000,000 2,966,646 337 >=337 27 B