EC2-TC16

EtherCAT Slave I/O Module with 16-channel Thermocouple Inputs
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16
EC2-TC16

Features

  • On the fly processing: EtherCAT
  • 2 x RJ-45 bus interface
  • Distance between stations up to 100 m (100 BASE-TX)
  • Support daisy chain connection
  • Built-In 16-channel Thermocouple Intputs
CE FCC RoHS WEEE

Introduction

The EC2-TC16 is an industrial slave I/O module built in 16-ch Thermocouple intputs. That provides 100Hz high-speed measurement and open wire detection for each channel. The module supports a variety of thermocouple input types, including Type J, K, T, E, R, S, B, N, C, L, M, and LDIN43710, and features an automatic cold-junction compensation function for all channels. It is equipped with the EtherCAT protocol and installed by daisy chain connection that provides a more scalable system with fewer wires. The EC2-TC16 has passed and verified by the conformance test tool, therefore eligible EtherCAT Master or configurator can manipulate it simply and implement your various applications easily.

Applications

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES EC2-TC16     CR DESCRIPTIONEtherCAT Slave I/O Module with 16-channel Thermocouple Inputs (RoHS)
This combination include other products.

Similar Products

EMS Protection
EFT (IEC 61000-4-4) Signal: 1 KV Class B; Power: 1 KV Class B
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
Surge (IEC 61000-4-5) ± 1 kV Class A
Analog Input
Channels 16
Type Thermocouple (J, K, T, E, R, S, B, N, C, L, M, LDIN43710)
Resolution 16-bit
Accuracy ±0.1 % of FSR ( 25℃ )
Sampling Rate 100 Hz ( per channel )
Overvoltage Protection 30 VDC
Individual Channel Configuration Yes
Open Wire Detection Yes
EtherCAT
Ports EtherCAT, 2 X RJ45
Node ID Up to 256
Distance Between Stations Max. 100 m (100 Base-Tx)
Data Transfer Medium Ethernet/EtherCAT cable (min. CAT5), shielded
Cycle Time 100 us
Distributed Clocks Yes
Power
Input Range +24 VDC
Consumption 3 W
Mechanical
Casing Metal with IP40
Dimensions (mm) 83 x 122 x 65 (W x L x D)
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -30 ~ +80°C
Humidity 10 ~ 90% RH, Non-condensing