DN-843I-CT-10

3-channel 10 A Current Transformer
DN-843I-CT-10
DN-843I-CT-10
DN-843I-CT-10
DN-843I-CT-10

Features


• AC/DC Source Input
• Linear Attenuation Ratio
• High Current Input Measurement
• Isolation Input
• Easily Wire Connection
CE UKCA FCC RoHS WEEE

Introduction

The maximum input range is from ±1 A to +/- 50 A and can be attenuated to from ±1.6 V to ±10 V. The "I" version provide 3000 VDC intra-modules isolation and 3000 VDC channel to channel isolation to avoid the noise interference from inputs to outputs or channel to channel. It can be used with the analog input modules such as I-7017 and I-87017 etc. to measure the high current.

Applications

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES DN-843I-CT-10     CR DESCRIPTION3-channel 10 A Current Transformer (RoHS)
This combination include other products.

Similar Products

EMS Protection
ESD (IEC 61000-4-2) ±4 kV contact for power line, input and output channels, ±8 kV air for random point
CT
Type Solid Core (closed)
Inside Diameter 20.4 X 10.4 mm
Analog Input
Channels 3
Type AC/DC Current
Range ±10 A
Accuracy 1% of FSR
Bandwidth 50 KHz
Input Impedance > 1 MΩ
Channel-to-Channel Isolation Yes, 3000 Vrms
Intra-module Isolation 3000 VDC
Analog Output
Channels 3
Type AC/DC Voltage
Range ±10 Vpp
Power
Input Range +10 VDC ~ +24 VDC
Consumption 1.2 W
Mechanical
Casing Plastic
Dimensions (mm) 148 x 83 x 39 (W x L x D)
Installation DIN-Rail Mounting
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +75 °C
Humidity 10 ~ 90% RH, Non-condensing