BNET-2107M

BACnet/IP I/O module with 8-ch DI and 8-ch DO
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M
BNET-2107M

Features

  • Read/Write 8 BO, 8 BI and 8 PIV via BACnet/IP
  • Act as BACnet/IP Server
  • Support Web-based configuration
  • High reliability in harsh environments
  • DIN-Rail mountable
CE UKCA RoHS WEEE

Introduction

BACnet (Building Automation and Control Network) is a communication protocol specifically designed for building automation and control systems. It was established by the American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) in 1995 and has been adopted by the International Organization for Standardization (ISO) as a standard (ISO 16484-5). BACnet aims to enable interoperability between devices from different manufacturers, particularly those involved in Building Management Systems (BMS), such as HVAC, lighting control, security systems, fire alarms, and more. BACnet supports various transmission media, including IP networks, RS-485, ARCNET, and MS/TP (Master-Slave/Token Passing), making it adaptable to different installation environments. Its ability to integrate and manage multiple devices in automation systems has made it one of the most widely used communication protocols in modern smart buildings.

The BNET-2107M is a BACnet/IP IO module, featuring 8 digital input and 8 digital output channels. The module contains multiple BACnet objects, including Device, BO, BI, PIV, and supports various BIBBS (such as DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM, DS-COV-B, etc.). The module has a built-in web server, allowing users to easily and securely configure the module remotely via a web interface.

Applications

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES BNET-2107M     CR DESCRIPTIONBACnet/IP I/O module with 8-ch DI and 8-ch DO (RoHS)
This combination include other products.

Similar Products

CPU Module
Watchdog Timer Yes
System
Security ID and Password
LED Indicators
Status Power, Ethernet and BIP status
Digital Input
Channels 8
Type Wet Contact
Sink/Source (NPN/PNP) Source(PNP)
ON Voltage Level +3.5 ~ +50VDC
OFF Voltage Level +1 VDC Max.
Overvoltage Protection +70 VDC
Digital Output
Channels 8
Sink/Source (NPN/PNP) Sink(NPN)
Load Voltage +3.5 VDC ~ 50 VDC
Load Current 700 mA/channel
Overvoltage Protection 60 VDC
Overload Protection Yes
Ethernet
Ports 1 x RJ-45, 10/100 Base-TX
BACnet/IP
Protocol BACnet/IP Server
Objects 1 Device, 8 BI, 8 BO, 8 PIV
BIBBs DS-RP-B, DS-RPM-B, DS-WP-B, DS-WPM-B, DS-COV-B, DM-DDB-B, DM-DOB-B, DM-DCC-B, DM-TS-B, DM-UTC-B, DM-RD-B
Power
Input Range +10VDC to +30VDC
Consumption 2.4W (0.1A @ 24VDC)
Mechanical
Casing Metal
Dimensions (mm) 33 x 120 x 106 (W x L x D)
Installation DIN-Rail Mounting
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -30 ~ +85 °C
Humidity 10 ~ 90% RH, Non-condensing