home > product > Solutions > Soft PLC, ISaGRAF & eLogger HMI > ISaGRAF > ViewPAC
 
ViewPAC-2000 Series (ISaGRAF based)
VP-2117
 
 

這個頁面上的內容需要較新版本的 Adobe Flash Player.

取得 Adobe Flash Player

 
Highlight Information
80186, 80 MHz CPU
MiniOS7 Inside
Development Software: ISaGRAF Ver.3
3 I/O Slots
IP65 Compliant Front Panel
STN LCD with English and Chinese Fonts
Rubber Keypad with 24 Keys
Operating Temperature: -15 ~ +55 °C
 

The ISaGRAF MiniOS7 ViewPAC Series (VP-2117) is the ISaGRAF PAC (Programmable Automation Controller) with graphic display and keypad. Each is equipped with an 80186 CPU (16-bit and 80 MHz) running a MiniOS7 operating system, a STN LCD, a rubber keypad, 3 or no I/O slots, and a variety of input/output ports (Ethernet, RS-232/485, etc.). Its operating system, MiniOS7, can boot up in a very short time (0.4 ~ 0.8 seconds). It has a built-in hardware diagnostic function, and supports the full range of functions required to access all high profile I-8K and I-87K series I/O modules, such as DI, DO, DI/DO, AI, AO, Counter/Frequency, motion control modules, etc. Users can also choose RS-485 Remote I/O modules (I-7000 series) or expansion units (RU-87Pn or I-87Kn) plugged with high profile I-87K serial I/O modules. Compared with traditional HMI + PLC solutions, ViewPAC reduces overall system cost, space and gives you all the best features of HMIs and PLCs.

 
MiniOS7 Embedded Operating System (DOS-like)
Embedded ISaGRAF Ver.3 SoftLogic
Support IEC 61131-3 Standard
Support Graphic and Keypad functions
Accepts max. 64 KB ISaGRAF code size
 
 
80186 CPU (16-bit & 80 MHz) 3 I/O Expansion Slots (support High Profile I/O Modules)
768 KB SRAM & 512 KB Flash 64 MB NAND Flash for Data Storage
IP65 Compliant Front Panel 10/100M Ethernet Port
Rubber Keypad 3 Serial Ports (RS-232, RS-485)
STN LCD with English and Chinese Fonts  
 
 
TOP | HOME
 
Measure Humidity and Temperature Values
via DL-100TM485
ISaGRAF PAC connects the Smart Meter ZigBee Wireless Solution
 
 
Stress Monitoring Application of Constructions SMS: Short Message Service
Integrate with CAN/CANopen Devices and Sensors Motion Control
Send Email with One Attached File Data Recorder and Data Logger
An Easy Way to Program the Fast FRnet Remote I/O Modules Data Exchange: Fbus or Ebus
Modbus RTU/TCP Slave Ports Detect I-8K/I-87K I/O status
Modbus RTU/ASCII Master Ports VIP Communication Security
Remote I/O Modules and Expansion module/board As a Modbus Gateway for the Remote I/O Modules
   
 
for "Applications Supporting List" & all applications
 
 
TOP | HOME
Models VP-2117
System Software
OS MiniOS7 (DOS-like embedded operating system)
Development Software
ISaGRAF Software ISaGRAF Ver. 3 IEC 61131-3 standard
Languages LD, ST, FBD, SFC, IL & FC
Max. Code Size 64 KB
Scan Time 2 ~ 25 ms for normal program
10 ~ 125 ms (or more) for complex or large program
CPU Module
CPU 80186, 80 MHz
SRAM 768 KB
Flash 512 KB
Flash Disk 64 MB NAND Flash
Dual Battery Backup SRAM 512 KB; data valid up to 5 years (for retain variables)
EEPROM 16 KB
NVRAM 31 bytes (battery backup, data valid up to 5 years)
RTC (Real Time Clock) Provide second, minute, hour, date, day of week, month, year
64-bit Hardware Serial Number Yes, for Software Copy Protection
Watchdog Timers Yes (0.8 second)
Communication Ports
Ethernet RJ-45 x 1, 10/100 Base-TX (Auto-negotiating, LED indicators)
COM 0 Internal communication with the I-87K High profile modules in slot 0 ~ 2
COM 1 RS-232 (RxD, TxD and GND) Program download port; Non-isolated
COM 2 RS-485 (Data+, Data-) with internal self-tuner ASIC; 2500 VDC isolated
COM 3 RS-232/RS-485 (RxD, TxD, CTS, RTS and GND for RS-232, Data+ and Data- for RS-485);
Non-isolated
MMI (Man Machine Interface)
LCD STN, 128 x 64 Dot Matrix LCD
Display Mode Text + Graphics
Text Font English + Simplified Chinese/Traditional Chinese
Rubber Keypad 24 keys
Buzzer Yes
LED Indicators 3 Dual-Color LEDs
(PWR, RUN, LAN1, L1,L2, L3; L1 ~ L3 for User Programmable)
I/O Expansion Slots
Slot Number 3
Note: For High Profile I-8K and I-87K Modules Only
Mechanical
Dimensions (W x L x H) 182 mm x 158 mm x 125 mm
Installation Panel Mounting
Ingress Protection Front panel: IP65
Environmental
Operating Temperature -15 ~ +55°C
Storage Temperature -30 ~ +80°C
Ambient Relative Humidity 10 ~ 90% RH (non-condensing)
Power
Input Range +10 ~ +30 VDC
Isolation 1 kV
Capacity 15 W
Consumption 6 W
Protocols  (Note that certain protocols require optional devices)
NET ID 1 ~ 255, user-assigned by software
Modbus RTU/ASCII Master A max. of 2 ports: COM1 ~ COM3 and COM5. (*) (To connect to other Modbus Slave devices.) 
A max. of Modbus_xxx Function Block amount for 2 ports: 128.
Modbus RTU Slave A max. of 2 ports: COM1 and one of COM2 or COM3.
(For connecting ISaGRAF, PC/HMI/OPC Server and HMI panels.)
Modbus TCP/IP Slave Ethernet port supports Modbus TCP/IP Slave Protocol for connecting ISaGRAF & PC/HMI up to 6 connections.
User-defined Protocol Custom protocols can be applied at COM1~3 and COM5~16 using Serial communication function blocks. (*)
Remote I/O One of COM2 or COM3 supports I-7000 I/O modules, I-87K base + I-87K Serial I/O boards, or RU-87Pn + I-87K High Profile I/O boards as remote I/O. A max. of 64 I-7000/87K remote I/O modules can connect to one PAC.
Fbus Built-in COM3 Port to exchange data between ICP DAS’s ISaGRAF PACs.
Ebus Used to exchange data between ICP DAS ISaGRAF Ethernet PACs via the Ethernet port.
Send Email Provide functions to send email to a max. of 10 receivers with a single attached file via the Ethernet port through internet. The max. of file size is about 488 KB.
SMS:Short Message Service One of COM3 or COM5 can link to a GSM modem to support SMS. The user can request data/control the controller via a cellular phone. The controller can also send data and alarms to the user’s cellular phone. (*) Optional GSM Modem: GTM-201-RS232 (850/900/1800/1900 GSM/GPRS External Modem)
CAN/CANopen A max. of 3 ports: COM1, 3 or COM5 ~ COM12 (*) can connect to one I-7530 (converter: RS-232 to CAN) to support CAN/CANopen devices and sensors. One PAC supports a max. of 3 RS-232 ports to connect a max. of 3 I-7530. (FAQ-086)
FRnet I/O Enable a max. of 3 pcs. I-8172W boards to be used to connect to FRnet I/O modules, such as FR-2053, FR-2057, FR-32R, FR-32P. (Max. 768-ch. DI + 768-ch. DO)
Optional I/O Functions  (Refer to the ISaGRAF PAC I/O Selection Guide for I/O Module list)
PWM Output High Speed PWM Module I-8088W, 8-ch PWM outputs, software support 1 Hz ~ 100 kHz (non-continuous),
duty: 0.1 ~ 99.9%
DO Module as PWM 8-ch. max. 500 Hz max. For Off=1 & On=1 ms.
Output square wave: Off: 1 ~ 32766 ms, On: 1 ~ 32766 ms.
Optional DO Boards: I-8037W, 8041W, 8041AW, 8042W, 8050W, 8054W, 8055W, 8056W, 8057W, 8060W, 8063W, 8064W, 8068W, 8069W.
(Relay Output boards cannot generate fast square wave)
Counters, Encoder, Frequency Parallel DI Counter 8-ch. max. for 1 controller. Counter Val: 32-bit.; 500 Hz max.
Min. ON & OFF width must >1ms
Optional DI boards: I-8040W, 8040PW, 8042W, 8046W, 8048W, 8050W, 8051W, 8052W, 8053W, 8053PW, 8054W, 8055W, 8058W, 8063W.
Serial DI Counter Counter input: 100 Hz max. Counter value: 0 ~ 65535 (16-bit) 
Optional serial I-87K DI boards: I-87040W, 87046W, 87051W, 87052W, 87053W, 87053W-A5, 87054W, 87055W, 87058W, 87059W, 87063W.
Remote DI Counter All remote I-7000 & I-87K DI modules support counters. 100 Hz max. value: 0 ~ 65535
High Speed Counter I-87082W: 100 kHz max. 32-bit;
I-8084W: 250 kHz max. 32-bit
Encoder I-8093W: 3-axis Encoder Module, max. 1M Hz for quadrant input mode, max. 4M Hz for
              pulse/direction and cw/ccw input mode. (FAQ-112)
I-8084W: 250 kHz max., 4-ch encoder, can be pulse/direction, or Up/Down or A/B phase
              (Quad. mode); Not support Encoder Z-index. (FAQ-100)
Frequency I-87082W: 2-ch, 1 Hz ~ 100 kHz;
I-87088W: 8-ch, 0.1 Hz ~ 500 kHz;
I-8084W: 8-ch, 1 Hz ~ 250 kHz;
Motion Motion Control Can integrate with one I-8091W (2-axis) or two I-8091W (4-axis) to do motion control.
Ethernet communication is also available when doing motion control.
* Note: The COM5 ~ COM16 ports are located in the expansion boards if they are installed in slots 0 ~ 2 of VP-2117.
* ISaGRAF FAQ: www.icpdas.com > Support > FAQ > ISaGRAF Soft-Logic PAC
* ICP DAS recommends using NS-205/NS-208 or RS-405/408 (Ring Switch) Industrial Ethernet Switches.
 
TOP | HOME
VP-2117 CR ISaGRAF based ViewPAC with 3 I/O Slots (English + Simplified Chinese Font) (RoHS)
VP-2117-TC CR ISaGRAF based ViewPAC with 3 I/O Slots (English + Traditional Chinese Font) (RoHS)
 
ISaGRAF Development Software
ISaGRAF-256 ISaGRAF Workbench Software Ver.3 (256 I/O Tags) with one USB Dongle
ISaGRAF-32 ISaGRAF Workbench Software Ver.3 (32 I/O Tags)
Note: No upgrade service from ISaGRAF-32 to ISaGRAF-256 is available.
(ISaGRAF-32 can be used to control more than 32 I/O tags. Please refer to Ch. 3.4 of the ISaGRAF User Manual.)
 
Power Supplies for DIN RAILS
DP-660 24 V/2.5 A, 5 V/0.5 A Power Supply (Upright)
DP-665 24 V/2.5 A, 5 V/0.5 A Power Supply (Lie-flat)
DP-1200 CR 24 V/5 A Power Supply
Converter
I-7560 CR USB to RS-232 Converter (RoHS)
I-7561 CR USB to RS-232/422/485 Converter (RoHS)
Ethernet Switch
NS-205 CR / NS-208 CR 5-port / 8-port Unmanaged Industrial 10/100 Ethernet Switch with Plastic Case (RoHS)
 
TOP | HOME
 