這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player

home > product > solutions > remote i/o modules/units > tWF-series > tWF-DA1PD2R1
 
tWF-DA1PD2R1
1-channel Analog Output, 2-channel Digital Input and 1-channel Relay Output Module
 
 
~ NEW ~  
  • Wi-Fi communication remote I/O module
  • Both Access Point (AP) & Station (STA) mode support
  • PC utility, Android APP, Web browser support (HTML)
  • MODBUS TCP support
  • Wide power supply range
  • Wide operating temperature range
  • Photo couple Isolation input, Relay Isolation output
  • Digital input 32-bit counter
  • 0 ~ 10V 12 bit 4096 resolution DA Converter output
  • Simplify Light control function
Model: tWF-DA1PD2R1
*Asia Only
The tWF-DA1PD2R1 module have WLAN connection complies with the IEEE802.11b/g/n standards. With the popularity of 802.11 network infrastructure, the tWF-DA1PD2R1 module make an easy way to incorporate wireless connectivity into monitoring and control systems. They also support Modbus TCP protocol and the network encryption configuration, which makes perfect integration to SCADA software, HMI Modbus APP and offer easy and safe access for users from anytime and anywhere.
 
  • Building Automation
  • Security Automation
  • Machine Automation
  • Factory Automation
  • Remote Diagnosis
  • Remote Maintenance
  • Simplify Light control system
  • Testing Equipment
 
OS Access Point(AP) Station(STA)
Windows Utility IP Scanner (1) & Utility
Android APP IP Scanner (1) & APP
Web Browser Yes Yes
Modbus TCP Yes (2) Yes (2)
(1) Free IP Scanner
(2) PC or Android Freeware
 
Analog Output
Channels 1
Type 0 ~ 10 V, 0 ~ 20 mA, 4 ~ 20 mA
On Voltage Level 12-bit
Accuracy +/-0.1% of FSR
DA Output Response Time 10ms
Voltage Output Capability 20mA
Current Load Resistance 500Ω
Digital Input
Channels 2
Input Type Dry Contact: Sink
Dry Contact Level Off Voltage Level: Open
On Voltage Level: Close to GND
Counters Channels 2
Max. Counts 32-bit (4294967295)
Max. Input Frequency 20 Hz
Photo-Isolation 3750 VDC
Digital Output
Channels 1
Output Type Form A Relay
Contact Rating (Resistive Load) DC 30V/5A
AC 250V/5A
Relay Operate Time 5 ms (Max.)
Relay Release Time 5 ms (Max.)
 
Communication
Interface Wi-Fi 2.4 G
Standard IEEE 802.11 b/g/n
Encryption WEP, WPA/WPA2-PSK
Mode Access Point (AP) & Station (STA)
IP Configuration DHCP Server (AP, 1 client), DHCP Client, Static IP (STA)
Service TCP, HTTP, Modbus TCP
LED Indicators
Power One 2 colors LED, Blue for System status, Red for Connective status/Locator
Isolation
Intra-module Isolation,Field-to-Logic 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power
Power Requirements
Reverse Polarity Protection Yes
Powered from Terminal Block 9 ~ 48 VDC
Consumption 0.7 W Max.
Mechanical
Dimensions (W x L x H) 52 mm x 97 mm x 27 mm
Installation DIN-Rail Mounting
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +75 °C
Humidity 10 ~ 95% RH, Non-condensing
 
tWF-DA1PD2R1 CR 1-channel DA Output, 2-channel Isolated Dry Digital Input, 1-channel Relay Output Module (RoHS)
 
TOP | HOME
 

這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player