home > product> solutions > remote i/o modules/units > tM series Modules (DCON, Modbus RTU, Modbus ASCII Protocol)
 
 
 
   
 
The tM series is a family of network data acquisition and control modules, providing digital I/O functions. The modules can be remotely controlled through an RS-485 serial bus by using DCON and Modbus RTU protocols. The selectable transmission speed of the RS-485 port is up to 115,200 bps. Modbus has become a de facto standard communications protocol in industry, and is now the most commonly available means of connecting industrial electronic devices. This makes the tM series perfect integration with the HMI, SCADA, PLC and other software systems.

The functionality of the tM series is the same as the M-7000 series. The tM series tiny RS-485 I/O modules support various I/O types, like photo-isolated digital input, relay contact, photoMOS relay, and open-collector output.

The tM series provides dual watchdog: module watchdog and host watchdog. The module watchdog is designed to automatically reset the microprocessor when the module hangs. The host watchdog monitors the host controller (PC or PLC), and the output of the module can go to predefined safe value state when the host fails.

For maximum space savings, the tM series is offered in an amazing tiny form-factor that makes it can be easily installed in anywhere, even directly embedded into a machine. It is equipped with two removable terminal block connectors for easy wiring.
 
  • Cost-effective remote I/O modules
  • Supports Modbus RTU and DCON protocols
  • Isolated Digital Input and Output
  • RS-485 bus supports baud rate up to 115200 bps
  • Dual-watchdog with power-on and safe value
  • Terminal block connector for easy wiring
  • Tiny form-factor and low power consumption
  • RoHs compliant with no Halogen
  • Made from fire retardant materials (UL94-V0 Level)
  • Easy DIN-Rail mounting
 
The brief comparison is as the following table. Besides those regular RS-485 I/O modules, we can also provide some ODM modules.
 
Model Name tM series I-7000 M-7000
Pictures
Communication
Protocol DCON, Modbus RTU, Modbus ASCII DCON DCON, Modbus RTU
Data Format (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1) (N,8,1)
Max. Nodes 32 256
Bias resistor Yes, 10 KΩ No (Note1)
Dual Watchdog Yes, Module (2.3 second),
Communication (Programmable)
Yes, Module (1.6 second),
Communication (Programmable)
I/O
DIO max. channel 8 16
AIO Resolution 12/14 bits 12/16 bits
Max. channel 8 (tM-AD8) 20 (I-7017Z, M-7017Z)
Individual Channel Configuration - Yes
Display
Power and Communication LED Yes Yes
I/O Status LED - Yes (for D version only)
7-Segment LED - Yes (for D version only)
Mechanical
Dimensions (W x L x D) 52 mm x 98 mm x 27 mm 72 mm x 123 mm x 35 mm
Note1: The RS-485 master is required to provide the bias. Otherwise, the tM-SG4 or SG-785 should be added to provide the bias.
All ICP DAS controllers and converters provide the bias.
 