這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player

home > product > solutions > remote i/o modules/units > tm-series > tM-P4C4
 
tM-P4C4
4-channel Isolated Digital Input and 4-channel Isolated Digital Output Module
 
 
     
  • Sink-type Digital Outputs
  • Source-type Digital Inputs
  • Photocouple Isolation
  • All Channels Can Be Used As 16-bit Counters
  • Dual Watchdog
  • Configurable Power-on Value Settings
  • Configurable Safe Value Settings
  • Cost-effective
  • Wide Operating Temperature Range: -25 °C ~ +75 °C
   
Model: tM-P4C4    
 
The tM-P4C4 provides 4 channels for digital input and 4 channels for digital output, each of which features photocouple isolation. The tM-P4C4 supports sink-type output with short circuit protection, while input is source-type. All input channels can be used an 16-bit counters. There are options for configuring power-on and safe digital output values. 4 kV ESD protection and 3750 VDC intra-module isolation are also provided.
 
  • All Kinds of On/Off Control
  • Industrial Automation
  • Industrial Machinery
  • Building Automation
  • Food and Beverage Systems
  • Semiconductor Fabrication
  • Control Systems
 
Digital Input/Counter
Input Channels 4
Type Wet Contact (Source)
On Voltage Level +3.5 VDC ~ 50 VDC
Off Voltage Level +1 V max.
Input Impedance 10 KΩ, 0.66 W
Counters Channels 4
Max. Counts 65535 (16-bit)
Max. Input Frequency 100 Hz
Min. Pulse Width 5 ms
Overvoltage Protection 70 VDC
Digital Output
Output Channels 4
Type Isolated Open Collector (Sink)
Max. Load Current 700 mA/channel
Load Voltage 3.5 VDC ~ 50 VDC
Overvoltage Protection 60 VDC
Overload Protection Yes
Short-circuit Protection Yes
Power On Value Yes, Programmable
Safe Value Yes, Programmable
 
Communication
Interface RS-485
Format (N, 8, 1), (N, 8, 2), (O, 8, 1), (E, 8, 1)
Baud Rate 1200 ~ 115200 bps
Protocol DCON, Modbus/RTU, Modbus/ASCII
Dual Watchdog Yes, Module (2.3 seconds), Communication (Programmable)
LED Indicators
Power 1 LED as Power Indicator
Isolation
Intra-module Isolation,Field-to-Logic 3750 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power
Power Requirements
Reverse Polarity Protection Yes
Powered from Terminal Block Yes, 10 ~ 30 VDC
Consumption 0.5 W Max.
Mechanical
Dimensions (W x L x H) 52 mm x 98 mm x 27 mm
Installation DIN-Rail Mounting
Environment
Operating Temperature -25 °C ~ +75 °C
Storage Temperature -30 °C ~ +75 °C
Humidity 10 ~ 95% RH, Non-condensing
 
tM-P4C4 CR 4-channel Isolation Digital Input and 4-channel Isolation Digital Output Module (RoHS)
 
tM-7561 CR Isolated USB to RS-485 Converter (RoHS)
tM-7520U CR Isolated RS-232 to RS-485 Converter (RoHS)
tM-7510U CR Isolated RS-485 Repeater (RoHS)
MDR-20-24 CR 24 W Single Output Industrial DIN Rail Power Supply (RoHS)
 
TOP | HOME
 

這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player