這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player

home > product > solutions > Industrial IoT Products > Sensor Series Selection Guide > iSN-101/iSN-101/DIN
 
iSN-101/iSN-101/DIN
Liquid Leak Detection Module
 
~ NEW ~  
Model: iSN-101 Model: iSN-101/DIN
 
  • 1-ch Liquid Leak Detection
  • Water Leakage detection triggers and audible alarm
  • A mute button to silence the audible alarm
  • Two LED indicators to display the status of the power and the alarm
  • Relay Output for Water Leakage Alarm
  • Liquid Leak Detection Cable and Extended Cable can be up to 500 meters
  • Sensitivity adjustable detection
  • Supports the DCON and the Modbus RTU Protocols
  • Embedded Dual Watchdog
  • Wide Operating Temperature Range: -25 to +75°C
  • Tiny Form Factor with Easy Screw Mounting
 
The iSN-101 Liquid Leak Detection Module is a low-cost intelligent liquid leak detection device that can be used to directly control Relay Output. No additional conversion module is needed and the iSN-101 can be easily integrated with a variety of monitoring systems to achieve remote alarm and remote device control. The iSN-101 Liquid Leak Detection module can be used to monitor double-core leader cable lengths of up to 500 meters, and can be used with both the extended cable and its included liquid leak detection cable. If liquid is detected, the controller immediately activates the output relay - the normally open, normally closed passive output signal . The module can be easily integrated with other collection hosts connected to the network. The iSN-101 is suitable for real-time leak detection in critical locations, such as computer room base stations, warehouses, libraries, museums and industrial sites, and also for air handling equipment, refrigeration units, liquid containers, or pump tanks, etc., where there is a need to monitor any leakage of the equipment.

When required, communication with the iSN-101 can be programmed based on the Modbus RTU protocol, with the added benefi t that different addresses can be confi gured via hardware to allow for Modbus RTU communication.
 
The iSN-101 is a leakage detection module used in water pipe leak monitoring in buildings with two working modes.
1. Work with the water sense cable that installed near the possible leaking pipe or area to detect leakage with alarm.
2. Work with the water leakage probe that installed in fi xed possible leak locations to detect.
The leakage monitoring is applied to the water pipes, fi re pipes and sewage pipes of buildings, as well as the detecting of domestic water, drainage and electric equipment, which can eff ectively achieve water saving and ensure the safety of living. The iSN-101 can detect leakages, send out signal and alarms, combine with the WISE IoT Edge Controller or TPD/VPD Touch HMI, and to further integrate with the mobile APP or community system.
 
Analog Input
Channels 1
Wiring Cables Length 500 meters (include Liquid Leak Detection Cable and Extended Cables)
Sound Off Button The button is used to stop the audible alarm.
Sensitivity Adjustment Range 26 KΩ ~ 580 KΩ
Detection of Pure Water Yes, 2uS/cm
Water Leakage Alarm Yes, 1 Sec ( Built-in Buzzer)
Relay Output for Water Leakage Alarm
Channels 1
Form C Relay 0.5 A @ 125 VAC
2 A @ 30 VDC
 
Communication
Interface RS-485
Format N,8,1 / O,8,1 / E,8,1 / N,8,2
Baud Rate Software Configuration: 1200 ~ 115200 bps
Protocol Modbus RTU or DCON
Node Addresses 96 ~ 127 for hardware configuration
0 ~ 255 for software configuration
LED Indicators
LED Indicators 1 as Power Indicator. 1 as Alarm Indicator.
EMS Protection
ESD (IEC 61000-4-2) ±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power
Power
Reverse Polarity Protection Yes
Input Voltage Range 10 to 30 VDC
Consumption 1.5 W Max.
Mechanical
Dimensions (W x L x H) 83 mm x 70 mm x 29 mm
Installation DIN-Rail
Environment
Operating Temperature -25 to +75°C
Storage Temperature -30 to +80°C
Humidity 10 to 90% RH, Non-condensing
 
iSN-101 CR 1-channel Liquid Leak Detection Module (RoHS)
iSN-101/DIN CR 1-channel Liquid Leak Detection Module (DIN Rail mount) (RoHS)
iSN-101/S CR
iSN-101/S/DIN CR
1-channel Liquid Leak Detection Module (RoHS)
Includes an iSN-101 Module, a 1m Liquid Leak Detection Cable and 3m Extended Cable.
iSN-101/S2 CR
iSN-101/S2/DIN CR
1-channel Liquid Leak Detection Module (RoHS)
Includes an iSN-101 Module, a 3m Liquid Leak Detection Cable and 3m Extended Cable.
iSN-101/S3 CR
iSN-101/S3/DIN CR
1-channel Liquid Leak Detection Module (RoHS)
Includes an iSN-101 Module and a Leakage Probe.
iSN-101/S CR = iSN-101 +
CA-LLD-DC100-L010 + CA-LLD-EC-L030
iSN-101/S2 CR = iSN-101 +
CA-LLD-DC100-L030 + CA-LLD-EC-L030
iSN-101/S3 CR =
iSN-101 + CA-LLD-DP100
 
tM-7520U CR RS-232 to RS-485 converter (RoHS)
tM-7561 CR USB to RS-485 converter (RoHS)
I-7514U CR 4-channel RS-485 Hub (RoHS)
CA-LLD-DC100-L010 Liquids Leak Detection, Water Detection Cable w/o Position, 1m length
CA-LLD-DC100-L030 Liquids Leak Detection, Water Detection Cable w/o Position, 3m length
CA-LLD-DC100-L100 Liquids Leak Detection, Water Detection Cable w/o Position, 10m length
CA-LLD-DC100-L300 Liquids Leak Detection, Water Detection Cable w/o Position, 30m length
CA-LLD-DC100-L500 Liquids Leak Detection, Water Detection Cable w/o Position, 50m length
CA-LLD-EC-L030 3m Leader Cable
CA-LLD-DP100 Leakage Probe
ASO-0051 180 Hold-Down Clip (include 50 pcs)
ASO-0052 90 Hold-Down Clip (include 50 pcs)
 
TOP | HOME
 

這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player