M-6026U-32
16-channel Universal Input and 16-channel Universal Output
 
~ NEW ~  
 
Model: M-6026U-32  
 
  • Universal Inputs and Universal Outputs
  • Status LED for Universal inputs and outputs
  • Integrated Design Allows You to Take Advantage of Inputs and Outputs
  • Any Universal I/O point can be configured as analog input/output, digital input or counter input
  • 100 VDC Over Voltage Protection for Universal Inputs
  • Open Wire Detection for +4 to +20 mA Outputs
  • Support Modbus RTU Protocol
  • Easy Mounting and Connection
  • Space Saving Design
  • Wide Operating Temperature Range: -25°C to +75°C
 
The M-6026U-32 of distributed I/O provides a wide variety of input, output, and smart control solutions, all of which are based on a single universal hardware platform. The M-6026U-32 combines inputs and outputs, saving your time and space when both are at a premium. Since M-6032U-32 feature both inputs and outputs on the same board, retailers can reduce the space requirement for I/O boards by as much as 50%! Traditional I/O board schemes required retail operators to mount separate input and output boards within an enclosure, increasing the time and cost to mount the boards. The M-6000 I/O boards are communications devices needed to connect to the facility management system to control refrigeration, HVAC and lighting systems.
 
  • Heating system in buildings
  • Ventilation system
  • Air-conditioning system
  • HVAC control, lighting control, door monitoring
 
Universal Input
Channels 16
Type 0 ~ 2.5V, 0 ~ 5 V, 0 ~ 10 V, 0 to 20 mA, 4 to 20 mA, Pt1000, Dry Contact Digital Input
Resolution 16-bit
Accuracy ±0.1% of FSR
Digital Input On Level Close to GND
Off Level OPEN
Over Voltage Protection 100 VDC
Universal Output
Channels 16
Type 0 to 20 mA, 4 to 20 mA, 0 to 10 V
Resolution 12-bit
Accuracy ±0.2% of FSR
Voltage Output Capability 10 V@ 20mA
Open Wire Detection for Current Output Yes, Only 4 to 20 mA
 
RS-485
Interface RS-485 x 1
Format N, 8, 1
Baud Rate 1200 to 115200 bps
Protocol Modbus/RTU
Dual Watchdog Yes, Module (2.3 seconds), Communication (Programmable)
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
±8 kV Air for Random Point
Power Requirements
Power from Terminal Block 24 VAC or 24 VDC
Fuse Protection 1 A
Power Consumption 14 W Max.
Mechanical
Dimensions (W x L x H) 240 mm x 135 mm x 65 mm
Environment
Operating Temperature -25°C to +75°C
Storage Temperature -40 to +80°C
Relative Humidity 10 ~ 95% RH, Non-condensing
 