M-2018-16
16-channel Analog Input Module |
|
|
~ NEW ~ |
|
|
 |
- 16-channel Differential Analog Input
- ±120 VDC Overvoltage Protection
- Current, Voltage or Thermocouple Input
- 3000 VDC Intra-module Isolation
- Adjustable CJC offset
- Open Thermocouple Detection
- Dual Watchdog
- Wide Operating Temperature Range: -25°C to +75°C
|
|
 |
|
|
Model: M-2018-16 |
|
|
|
|
 |
The M-2018-16 is an analog input module that includes 16 differential analog input channels. The voltage input range can be from ±15 mV to ±2.5 V, the current input range can be either +4 to +20 mA, 0 to +20 mA, or ±20 mA, and types J, K, T, E, R, S, B, N, C, L, M, LDIN43710 thermocouple can be used for the thermocouple input. Overvoltage protection of up to 120 VDC is provided. The module also features per-channel open wire detection for the thermocouple input types, and provides 4 kV ESD protection as well as 3000 VDC intra-module isolation. |
|
 |
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
|
|
 |
Analog Input |
Channels |
16 |
Wiring |
Differential |
Sensor
Types |
Thermocouple |
J, K, T, E, R, S, B, N, C |
Voltage |
±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V |
Current |
±20 mA, 0 ~ +20 mA, +4 ~ +20 mA (requires an optional external 125 Ω resistor) |
Resolution |
16-bit |
Accuracy |
0.1% of FSR |
Sampling Rate |
10 Hz (Total) |
Input Impedance |
> 400 kΩ |
Common Voltage Protection |
25 VDC |
Individual Channel Configuration |
- |
Overvoltage Protection |
120 VDC |
Open Wire Detection (for thermocouple only) |
Yes |
Temperature Outputs Consistency |
- |
Stable Temperature Output in the Field |
- |
|
|
 |
Communication Interface |
Interface |
RS-485 |
Bias Resistor |
Switch Selectable (10 kΩ resistor) |
Format |
(N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1) |
Baud Rate |
1200 to 115200 bps |
Protocol |
Modbus RTU, DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicators/Display |
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
I/O LED Indicators |
- |
7-segment LED Display |
- |
Isolation |
Intra-module Isolated, Field-to-Logic |
3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±4 kV Contact for each Terminal |
±8 kV Air for Random Point |
EFT (IEC 61000-4-4) |
±4 kV for Power Line |
Surge (IEC 61000-4-5) |
±1 kV for Power Line |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +48 VDC |
Consumption |
0.5 W |
Mechanical |
Dimensions (W x L x H) |
132 mm x 157 mm x 31 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25 to +75°C |
Storage Temperature |
-40 to +85°C |
Humidity |
10 to 95% RH, Non-condensing |
|
|
 |
M-2018-16 CR |
16-channel Analog Input Module using the DCON and Modbus Protocols (RoHS) |
|
|
 |
tM-7520U CR |
RS-232 to RS-485 converter (RoHS) |
tM-7561 CR |
USB to RS-485 converter (RoHS) |
tM-SG4 CR |
RS-485 Bias and Termination Resistor Module (RoHS) |
I-7514U CR |
4-channel RS-485 Hub (RoHS) |
SG-770 CR |
7-channel Differential or 14-channel Single-ended Surge Protector (RoHS) |
SG-3000 Series |
Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input Transformers |
125 Ω, 0.1% DIP Resistor |
125 Ω External Resistor for use with Current input on I-7011/I-7012/I-7017/I-7018 series modules |
|
|
|
|
|
|
|