10-channel Thermocouple Input Module
 
   
Model: I-7018Z Model: M-7018Z
 
  • 10-channel Analog Input
  • Temperature Output Consistency
  • Stable Temperature Output in the Field
  • Current, Voltage and Thermocouple Input
  • Overvoltage Protection of up to 240 Vrms
  • Individual Channel Configuration
  • Open Thermocouple Detection
  • 4 kV ESD Protection
  • 3000 VDC Intra-module Isolation
  • Dual Watchdog
  • Wide Operating Temperature Range: -25 to +75°C
 
The I-7018Z/M-7018Z is a 10-channel universal Analog Input module with an RS-485 interface that is especially designed for extremely accurate thermocouple measurement and features automatic cold-junction compensation for each channel to ensure temperature output consistency and stable temperature output in the field. The innovative design of the enhanced model ensures that thermocouple measurement is more accurate than with the earlier design. Besides the thermocouple inputs, the I-7018Z/M-7018Z also supports voltage and current input. The voltage input range can be from +/-15 mV to +/-2.5 V. Up to 10 different types of Analog Input can be connected to a single module. Overvoltage protection of up to 240 Vrms is provided. The module also features per-channel open wire detection for the thermocouple and +4 ~ +20 mA input channels. The M-7018Z provides additional support for both the Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7018Z.
 
  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
 
Models I-7018Z M-7018Z
Analog Input
Channels 10
Wiring Differential
Sensor Types Thermocouple J, K, T, E, R, S, B, N, C, L, M, LDIN43710
Voltage ±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V
Current ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA (requires an optional external 125 Ω resistor)
Resolution 16-bit
Accuracy ±0.1% of FSR
Sampling Rate 10 Hz (Total)
Input Impedance > 400 kΩ
Common Voltage Protection ±200 VDC
Individual Channel Configuration Yes
Overvoltage Protection 240 Vrms
Open Wire Detection
(for thermocouple only)
Yes
Temperature Output Consistency Yes
Stable Temperature Output in the Field Yes
 
Models I-7018Z M-7018Z
Communication
Interface RS-485
Bias Resistor No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.)
Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate 1200 to 115200 bps
Protocol DCON Modbus RTU, DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator Yes, 1 as Power/Communication Indicator
I/O LED Indicator -
7-Segment LED Display -
Isolation
Intra-Module Isolation, Field-to-Logic 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
EFT (IEC 61000-4-4) ±4 kV to Power
Surge (IEC 61000-4-5) ±0.5 kV for Power Line
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 1.0 W
Mechanical
Dimensions (L x W x H) M-7018Z 116 mm x 73 mm x 35 mm
DB-1820 78 mm x 65 mm x 22 mm
DN-1822 103 mm x 96 mm x 27 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 to +75°C
Storage Temperature -40 to +85°C
Humidity 10 to 95% RH, Non-condensing
 
I-7018Z-G/S CR 10-channel Thermocouple Input Module using the DCON Protocol (Gray Cover) (RoHS)
Includes an I-7018Z Module and a DB-1820 Daughterboard.
I-7018Z-G/S2 CR 10-channel Thermocouple Input Module using the DCON Protocol (Gray Cover) (RoHS)
Includes an I-7018Z Module, a DN-1822 Daughterboard and a CD-2518D 1.8 m Cable.
I-7018Z-G/S3 CR ~ Available soon ~ 10-channel Thermocouple Input Module using the DCON Protocol (Gray Cover) (RoHS)
Includes an I-7018Z Module, a DN-1823 Daughterboard and a 15 cm Cable
M-7018Z-G/S CR 10-channel Thermocouple Input Module using the DCON and Modbus Protocols (Gray Cover) (RoHS)
Includes an M-7018Z Module and a DB-1820 Daughterboard.
M-7018Z-G/S2 CR 10-channel Thermocouple Input Module using the DCON and Modbus Protocols (Gray Cover) (RoHS)
Includes an M-7018Z Module, a DN-1822 Daughterboard and a CD-2518D 1.8 m Cable.
M-7018Z-G/S3 CR ~ Available soon ~ 10-channel Thermocouple Input Module using the DCON and Modbus Protocols (Gray Cover) (RoHS)
Includes an M-7018Z Module, a DN-1823 Daughterboard and a 15 cm Cable.
I-7018Z-G/S = I-7018Z + DB-1820
(The DB-1820 connects directly to the I-7018Z)
M-7018Z-G/S = M-7018Z + DB-1820
(The DB-1820 connects directly to the M-7018Z)
I-7018Z-G/S2 = I-7018Z + DN-1822
(The DN-1822 connects directly to the I-7018Z)
M-7018Z-G/S2 = M-7018Z + DN-1822
(The DN-1822 connects directly to the M-7018Z)
I-7018Z-G/S3 = DN-1823 Connects to the I-7018Z Directly
M-7018Z-G/S3 = DN-1823 Connects to the M-7018Z Directly
 
CD-2518D CR 25F-25M 1.8 m Cable with DIN-Rail Mount for the DB-1820 (RoHS)
CD-25015 CR 25F-25M 15 cm Cable with DIN-Rail Mount for the DB-1820 (RoHS)
4PAPP-006-G CR Plastic Rack (RoHS)
CD-25015
15 cm Cable + DB-1820
4PAPP-006-G
I-7018Z-G/S + CD-25015 + 4PAPP-006-G
M-7018Z-G/S + CD-25015 + 4PAPP-006-G
CD-2518D
1.8 m Cable + DB-1820
I-7018Z-G/S + CD-2518D
M-7018Z-G/S + CD-2518D
 
tM-7520U CR RS-232 to RS-485 converter (RoHS)
tM-7561 CR USB to RS-485 converter (RoHS)
tM-SG4 CR RS-485 Pull-high/Pull-low and Termination Resistor Module (RoHS)
I-7514U CR 4-channel RS-485 Hub (RoHS)
SG-770 CR 7 channel differential or 14 channel single-ended surge protector (RoHS)
SG-3000 Series Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input Transformers
125 Ω, 0.1% DIP Resistor 125 Ω External Resistor for use with Current Input on I-7011/I-7012/I-7017/I-7018 Series Modules
 
TOP | HOME
 

這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player