這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player

home > product> solutions > remote i/o modules/units > I-7000 & M-7000 > I-7015/I-7015P/M-7015/M-7015P
 
I-7015/I-7015P/M-7015/M-7015P
6-channel RTD Input Module
 
   
Model: I-7015/I-7015P Model: M-7015/M-7015P
 
  • 6-channel RTD Input
  • 3-wire RTD Input with Lead Resistance Elimination
  • High Resolution: 16-bit
  • Individual Channel Configuration
  • Open Wire Detection
  • 4 kV ESD Protection
  • 4 kV EFT Protection
  • 3000 VDC Intra-module Isolation
  • Dual Watchdog
  • Wide Operating Temperature Range: -25 to +75°C
 
The I-7015 is a series of 6-channel RTD input modules that are used for measuring temperatures using RTD sensors and each channel can be connected to a different type of sensor. The I-7015P/M-7015P is specifically designed for long-distance RTD measurement, and features automatic compensation for three-wire RTD, meaning that accurate measurements can be obtained regardless of the length of the wires. The I-7015 series is fully RoHS-compliant and features 4 kV ESD protection as well as 3000 VDC intra-module isolation. The M-7015/M-7015P supports both the Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7015/I-7015P.
 
  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
 
Models I-7015 I-7015P M-7015 M-7015P
Analog Input
Channels 6
Wiring 2/3-wire
Sensor Types Pt100, Pt1000, Ni120, Cu50, Cu100, Cu1000
Resolution 16-bit
Accuracy ±0.05% of FSR
Sampling Rate 12 Hz (Total)
Individual Channel Configuration Yes
Overvoltage Protection 120 VDC
Open Wire Detection Yes
3-wire RTD Lead Resistance Elimination - Yes - Yes
Resistance Measurement 3.2 kΩ Max.
 
Models I-7015 I-7015P M-7015 M-7015P
Communication
Interface RS-485
Bias Resistor No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.)
Format (N, 8, 1) (N, 8, 2) (E, 8, 1) (O, 8, 1)
Baud Rate 1200 to 115200 bps
Protocol DCON Modbus RTU, DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator Yes, 1 as Power/Communication Indicator
I/O LED Indicator -
7-Segment LED Display -
Isolation
Intra-Module Isolation, Field-to-Logic 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for each Terminal
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge (IEC 61000-4-5) -
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 1.1 W 1.2 W 1.1 W 1.2 W
Mechanical
Dimensions (L x W x H) 123 mm x 72 mm x 35 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 to +75°C
Storage Temperature -40 to +85°C
Humidity 10 to 95% RH, Non-condensing
 
I-7015 CR 6-channel RTD Input Module using the DCON Protocol (Blue Cover) (RoHS)
I-7015-G CR 6-channel RTD Input Module using the DCON Protocol (Gray Cover) (RoHS)
I-7015P-G CR 6-channel RTD Input Module with 3-wire Lead Resistance Elimination using the DCON Protocol (Gray Cover) (RoHS)
M-7015-G CR 6-channel RTD Input Module using the DCON and Modbus Protocols (Gray Cover) (RoHS)
M-7015P-G CR 6-channel RTD Input Module with 3-wire Lead Resistance Elimination using the DCON and Modbus Protocolsl (Gray Cover) (RoHS)
 
tM-7520U CR RS-232 to RS-485 converter (RoHS)
tM-7561 CR USB to RS-485 converter (RoHS)
tM-SG4 CR RS-485 Pull-high/Pull-low and Termination Resistor Module (RoHS)
I-7514U CR 4-channel RS-485 Hub (RoHS)
SG-770 CR 7 channel differential or 14 channel single-ended surge protector (RoHS)
SG-3000 Series Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input Transformers
 