這個頁面上的內容需要較新版本的 Adobe Flash Player。

取得 Adobe Flash Player

home > product> solutions > remote i/o modules/units > I-7000 & M-7000 > I-7012/I-7012D/I-7012F/I-7012FD
 
I-7012/I-7012D/I-7012F/I-7012FD
1-channel Analog Input Module
 
   
Model: I-7012/I-7012D Model: I-7012F/I-7012FD
 
  • Current or Voltage Input
  • High Resolution: 16-bit
  • High/Low Alarm (Digital Output)
  • 50 Hz Event Counter (Digital Input)
  • 100 Hz High Sampling Rate
  • 3000 VDC Intra-module Isolation
  • Dual Watchdog
  • Wide Operating Temperature Range: -25 to +75°C
 
The I-7012 is an Analog Input module that is designed for both voltage and current input types. In addition, the module provides 1 Digital Input channel as a 50 Hz event counter and 2 Digital Output channels that can be used as a high/low alarm. The I-7012 also features 3000 VDC intra-module isolation.

The I-7012F is an Analog Input module that is designed for both voltage and current input types. The sampling rate for the I-7012F is adjustable and can be switched between fast mode and normal mode depending on your requirements. In addition, the module provides 1 Digital Input channel as a 50 Hz event counter and 2 Digital Output channels that can be used as a high/low alarm. The I-7012F also features 3000 VDC intra-module isolation.
 
  • Building Automation
  • Factory Automation
  • Machine Automation
  • Remote Maintenance
  • Remote Diagnosis
  • Testing Equipment
 
Models I-7012 I-7012D I-7012F I-7012FD
Analog Input
Channels 1
Wiring Differential
Input Range ±150 mV, ±500 mV, ±1 V, ±5 V, ±10 V, ±20 mA (requires optional external 125 Ω resistor)
Resolution 16-bit
Accuracy Normal Mode 0.1%
Fast Mode - 0.5%
Sampling Rate Normal Mode 10 Hz
Fast Mode - 100 Hz
Input Impedance 20 MΩ
Common Voltage Protection ±100 VDC
Individual Channel Configuration -
Overvoltage Protection ±120 VDC
Digital Input
Channels 1
Contact Dry
Sink/Source (NPN/PNP) Source
ON Voltage Level Close to GND
OFF Voltage Level Open
Counter Yes, 50 Hz, 16-bit
Input Impedance 3 kΩ
Overvoltage Protection ±30 VDC
Digital Output
Channels 2
Type Open Collector
Sink/Source (NPN/PNP) Sink
Load Voltage +3.5 ~ +30 VDC
Max. Load Current 30 mA/Channel
Power-on Value Yes
Safe Value Yes
 
Models I-7012 I-7012D I-7012F I-7012FD
Communication
Interface RS-485
RS-485 Bias Resistor No (An RS-485 master is required to provide the bias.)
Format N, 8, 1
Baud Rate 1200 ~ 115200 bps
Protocol DCON
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicator/Display
System LED Indicator Yes, 1 as Power/Communication Indicator
I/O LED Indicator -
7-Segment LED Display - Yes - Yes
Isolation
Intra-Module Isolation, Field-to-Logic 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±2 kV Contact for each Terminal
EFT (IEC 61000-4-4) ±4 kV to Power Line
Surge (IEC 61000-4-5) ±0.5 kV for Power Line
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +30 VDC
Consumption 1.3 W 1.9 W 1.3 W 1.9 W
Mechanical
Dimensions (L x W x H) 123 mm x 72 mm x 35 mm
Installation DIN-Rail or Wall Mounting
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -40 ~ +85°C
Humidity 10 ~ 95% RH, Non-condensing
 
I-7012 CR 1-channel Analog Input Module using the DCON Protocol (Blue Cover) (RoHS)
I-7012-G CR 1-channel Analog Input Module using the DCON Protocol (Gray Cover) (RoHS)
I-7012D CR I-7012 with 7-segment LED Display (Blue Cover) (RoHS)
I-7012F CR 1-channel High Speed Analog Input Module using the DCON Protocol (16-bit) (Blue Cover) (RoHS)
I-7012FD CR I-7012F with 7-segment LED Display (16-bit) (Blue Cover) (RoHS)
 
tM-7520U CR RS-232 to RS-485 converter (RoHS)
tM-7561 CR USB to RS-485 converter (RoHS)
tM-SG4 CR RS-485 Pull-high/Pull-low and Termination Resistor Module (RoHS)
I-7514U CR 4-channel RS-485 Hub (RoHS)
SG-770 CR 7 channel differential or 14 channel single-ended surge protector (RoHS)
SG-3000 Series Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input Transformers
 