I-7011/I-7011D/I-7011P/I-7011PD
M-7011/M-7011D
1-channel Thermocouple Input Module |
|
|
|
|
|
 |
 |
 |
Model: I-7011/I-7011D |
Model: I-7011P/I-7011PD |
Model: M-7011/M-7011D |
|
|
 |
- 1-channel Analog Input
- Current, Voltage or Thermocouple Input
- Open Thermocouple Detection
- High Resolution: 16-bit
- 1-channel Digital Input as 50 Hz Event Counter
- 1-channel Digital Output as High/Low Alarm
- 3000 VDC Intra-module Isolation
- Dual Watchdog
- Wide Operating Temperature Range: -25 to +75°C
|
|
|
|
 |
The I-7011 series of modules feature current and voltage input, as well as thermocouple input. The module provides 1-channel Analog Input, 1-channel Digital Input that functions as a 50 Hz event counter, and 2-channel Digital Output that can be used as a high/low alarm. The module also features
open wire detection for the thermocouple input, and 3000 VDC intra-module isolation. The M-7011 supports both the Modbus RTU and DCON protocols, which can be configured via software, and all hardware specifications are the same as the I-7011. The I-7011P provides support for two additional thermocouple types, L and M. |
|
 |
- Building Automation
- Factory Automation
- Machine Automation
- Remote Maintenance
- Remote Diagnosis
- Testing Equipment
|
|
 |
Models |
I-7011
|
I-7011P
|
M-7011
|
I-7011D |
I-7011PD |
M-7011D |
Analog Input |
Channels |
1 |
Wiring |
Differential |
Sensor Types |
Thermocouple |
J, K, T, E, R, S, B, N, C |
J, K, T, E, R, S, B, N, C, L, M |
J, K, T, E, R, S, B, N, C |
Voltage |
±15 mV, ±50 mV, ±100 mV, ±500 mV, ±1 V, ±2.5 V |
Current |
±20 mA (requires optional external 125 Ω resistor) |
Resolution |
16-bit |
Accuracy |
0.1% of FSR |
Sampling Rate |
10 Hz (Total) |
Input Impedance |
> 400 kΩ |
Common Voltage Protection |
±5 VDC |
Individual Channel Configuration |
- |
Overvoltage Protection |
±5 VDC |
Open Wire Detection
(for thermocouple only) |
Yes |
Temperature Output Consistency |
- |
Stable Temperature Output in the Field |
- |
Digital Input |
Channels |
1 |
Contact |
Dry |
Sink/Source (NPN/PNP) |
Source |
ON Voltage Level |
Close to GND |
OFF Voltage Level |
Open |
Counter |
Yes |
Input Impedance |
3 kΩ |
Overvoltage Protection |
±30 VDC |
Digital Output |
Channels |
2 |
Type |
Open Collector |
Sink/Source (NPN/PNP) |
Sink |
Load Voltage |
+3.5 ~ +30 VDC |
Max. Load Current |
30 mA/Channel |
Power-on Value |
Yes |
Safe Value |
Yes |
|
|
 |
Models |
I-7011 |
I-7011P
|
M-7011
|
I-7011D |
I-7011PD |
M-7011D |
Communication |
Interface |
RS-485 |
Bias Resistor |
No (Usually supplied by the RS-485 Master. Alternatively, add a tM-SG4 or SG-785.) |
Format |
N, 8, 1 |
Baud Rate |
1200 to 115200 bps |
Protocol |
DCON |
Modbus RTU, DCON |
Dual Watchdog |
Yes, Module (1.6 Seconds), Communication (Programmable) |
LED Indicator/Display |
System LED Indicator |
Yes, 1 as Power/Communication Indicator |
I/O LED Indicator |
- |
7-Segment LED Display |
- |
Yes |
Isolation |
Intra-Module Isolation, Field-to-Logic |
3000 VDC |
EMS Protection |
ESD (IEC 61000-4-2) |
±2 kV Contact for each Terminal |
EFT (IEC 61000-4-4) |
±4 kV to Power Line |
Surge (IEC 61000-4-5) |
±0.5 kV for Power Line |
Power |
Reverse Polarity Protection |
Yes |
Input Range |
+10 ~ +30 VDC |
Consumption |
0.9 W |
1.5 W |
Mechanical |
Dimensions (L x W x H) |
123 mm x 72 mm x 35 mm |
Installation |
DIN-Rail or Wall Mounting |
Environment |
Operating Temperature |
-25 to +75°C |
Storage Temperature |
-40 to +85°C |
Humidity |
10 to 95% RH, Non-condensing |
|
|
 |
I-7011 CR |
1-channel Thermocouple Input Module using the DCON Protocol (Blue Cover) (RoHS) |
I-7011D CR |
I-7011 with with 7-segment LED Display (Blue Cover) (RoHS) |
I-7011P CR |
1-channel Thermocouple Input Module using the DCON Protocol (Blue Cover) (RoHS) |
I-7011PD CR |
I-7011P with 7-segment LED Display (Blue Cover) (RoHS) |
M-7011-G CR |
1-channel Thermocouple Input Module using the DCON and Modbus Protocols (Gray Cover) (RoHS) |
M-7011D-G CR |
M-7011 with 7-segment LED Display (Gray Cover) (RoHS) |
|
|
 |
tM-7520U CR |
RS-232 to RS-485 converter (RoHS) |
tM-7561 CR |
USB to RS-485 converter (RoHS) |
tM-SG4 CR |
RS-485 Pull-high/Pull-low and Termination Resistor Module (RoHS) |
I-7514U CR |
4-channel RS-485 Hub (RoHS) |
SG-770 CR |
7 channel differential or 14 channel single-ended surge protector (RoHS) |
SG-3000 Series |
Signal Conditioning Modules for Thermocouple, RTD, DC Voltage, DC Current and Power Input Transformers |
|
|
|
|
|
|
|