home > product> solutions > industrial wireless communication> ZigBee wireless solutions > ZT-2015
 
ZT-2015
Wireless 6-channel RTD Input Module with 3-wire RTD Lead Resistance Elimination
 
 
Model: ZT-2015
 
  • ISM 2.4 GHz Operating Frequency
  • Fully Compliant with 2.4 G / ZigBee Specifications
  • Wireless Transmission Range up to 700 m
  • External DIP and Rotary Switches for easy Configuration
  • GUI Configuration Software (Windows Version)
  • 3-wire RTD Input with Lead Resistance Elimination
  • Individual Channel Configuration
  • Open Wire Detection
  • Overvoltage Protection
  • DIN-Rail Mounting
 
The ZT-2015 offers 6 wireless input channels, each of which can be connected to different kinds of RTD sensors. It features automatic compensation for 3-wire RTD, with long-distance measurement capabilities so that it can measure accurately regardless of the length of the wires. Also the ZT-2015 is fully RoHS-compliant and has qualification for 4 kV ESD protection as well as 3000 VDC intra-module isolation. Users can easily configure the module address, protocol, checksum, ZB-PID, ZB-channel and type code settings using a combination of rotary and DIP switches.
 
Building Automation, Factory Automation, Machine Automation, Remote Maintenance, Remote Diagnosis, Testing Equipment.
 
Analog Input
Input Channels 6
Input Type 2/3-wire RTD
RTD Types Pt100, Pt1000, Ni120, Cu100, Cu1000
Resolution 16-bit
Sampling Rate 12 Samples/Sec. (Total)
Accuracy ±0.05%
Common Mode Rejection 150 dB
Normal Mode Rejection 100 dB
Open Wire Detection Yes
Overvoltage Protection 120 VDC/110 VAC
Individual Channel Configuration Yes
3-wire RTD Lead Resistance Elimination Yes
 
Communication Interface
Wireless Standards ZigBee 2007 Pro
Transmission Power 11 dBm (FCC Certificated) (Max. 19 dBm)
Antenna 2.4 GHz - 5 dBi Omni directional
Transmission Range (LoS) 700 m (Typical)
Certification FCC/FCC ID, CE (RED excluded)
Max. Slaves in a ZigBee Network 255
ZB-100R/ZB-100T Support -
Protocols Supports DCON and Modbus RTU Protocols
Dual Watchdog Yes, Module (1.6 Seconds), Communication (Programmable)
LED Indicators
Power 1 LED, Red
ZigBee Communication 1 LED, Green
Isolation
Intra-module Isolated, Field-to-Logic 3000 VDC
EMS Protection
ESD (IEC 61000-4-2) ±4 kV Contact for Power Line, Communication Line and each Channel,
±8 kV Air for Random Point
EFT (IEC 61000-4-4) ±4 kV for Power Line
Surge ( IEC 61000-4-5) ±3 kV for Power Line
Power
Input Voltage Range +10 VDC ~ +30 VDC
Power Consumption 1.5 W Max.
Mechanical
Flammability Fire Retardant Materials (UL 94V-0 Level)
Dimensions (L x W x H) 87 mm x 33 mm x 110 mm
Installation DIN-Rail
Environment
Operating Temperature -25 ~ +75°C
Storage Temperature -30 ~ +80°C
Relative Humidity 10 ~ 90% RH, Non-condensing
 
ZT-2015 CR Wireless 6-channel RTD Input Module with 3-wire RTD Lead Resistance Elimination (ZigBee Router) (RoHS)
Important Note: ZigBee Data Acquisition modules need a ZigBee host converter to coordinate the data transmission route. Please remember to order a ZT-2550, ZT-2570, and ZT-USBC ZigBee host converter when you purchase ZigBee Data Acquisition products.
 
MDR-20-24 24 VDC/1.0 A, 24 W Power Supply with DIN-Rail Mounting
ZT-2510 CR ZigBee Repeater (RoHS)
ZT-2550 CR RS-485/RS-232 to ZigBee Converter (Host)
ZT-2570 CR Ethernet/RS-485/RS-232 to ZigBee Converter (Host) (RoHS)
External Antenna 2.4GHz External Antenna, RP SMA Male (Plug)
Extension Cable 3S00x-1, RG58A/U x Meter Long RP-SMA (male) to RP-SMA (female)
 
TOP | HOME
 