~NEW~  
 
 
RM-22.22 Series
RM-22.22 Series
2 Polel, 20 A relay for direct 35 mm rail (EN 50022) mounting
 
 
     
 
  • Double phase switch 2 NO (DPST-NO)
  • 35 mm rail (EN 50022) mount
  • 17.4mm wide
  • Test button
  •  
         
       
     
     
     
    Model RM-20.22(Screwless)

    Contact Specification

    Contact configuration
    2 NO (DPST-NO)
    Rated current/Maximum peak current A
    20/30
    Rated voltage/Maximum switching voltage V
    250/400
    Rated load in AC1 VA
    5000
    Rated load in AC15 (230V AC) VA
    1000
    Single phase motor rating (230 V AC) kW
    -
    Breaking capacity DC1:30/110/220 V A
    20/0.3/0.12
    Minimum switching load mW(V / mA)
    1000(10/10)
    Standard contact material  
    AgSnO2
    Coil Specification
    Nominal voltage (UN) V DC
    24
    Rated DC power DC  
    1.25
    Operating range
    DC
    21.6~26.4 VDC
    Technical Data
    Mechanical life cycles
    500 ¡P 103
    Electrical life at rated load in AC1 cycles
    50 ¡P 103
    Operate/release time ms
    15/8
    Maximum impulse duration  
    continuous
    Insulation between coil and contacts (1.2/50 £gs) kV
    4
    Ambient temperature range ¢XC
    -40...+40
    Protection category  
    IP 20
    Approvals (according to type)  
     
         
       
     
     
     
    Contact specifications
    Nominal rate lamps
    incandescent (230V) W
    1000
    compensated fluorescent (230V) W
    360
    Insulation
    Dielectric strength
    between supply and contacts V AC
    3500
    between open contacts V AC
    2000
    between adjacent contacts V AC
    2000
    Other data
    Bounce time: NO / NC ms
    5/10
    Power lost to the environment 
    without contact current W
    1.2
    with rated current W
    3.2(22.21,22.23)
    5.2(22.22,22.24)
    Screw torque Nm
    0.8
    0.8
    Max. wire size  
     
    mm2
    AWG
    Coil terminals
    Contact terminals
    solid cable
    stranded cable
    solid cable
    stranded cable
    1x4/2x2.5
    1x2.5/2x2.5
    1x6/2x6
    1x6/2x4
    1x12/2x14
    1x14/2x14
    1x10/2x10
    1x102x12
    If the coil is operated for a prolonged period of time, adaquate ventilation of the relays must be provided - suggested gap of 9 mm between adjacent relays.
     
         
       
     
     
     
    DC version data
    Nominal voltage Coil code Operating range Resistance Consumption I at UN
    24 9.024 21.6 26.4 460 52.2
     
         
       
     
     
     