Q. I have a I-7060 module and a MMICON in the same RS-485 Network. My problem is that the I-7060 work  
    perfectly , but with the MMICON it can't work. I use the VB MSCOMM control to change the signal and with 
    the protocol analizer I see that the frame is correctly send but the MMICON doesn't responde me, but the 
    I-7050 work perfectly. If I use the RS232 comport, using a converter for rs232 to rs485, everything work ok. 
    Because I don't use the rtssignal

Ans:1. I recommended you to check the MMICON's J7 & J8. Refer to the Page 13 of Hardware manual.
       2. Set the J9 to INIT status and you will get the default setting(address=00; Baudrate=9600). Then set the I-7016   
           with address=01; Baudrate=9600. 
       3. Try to connect the Pin7 into Pin8 which is in your PC's COM port. Then the RTS signal will always enable.
¡@