M-7017mC-16-G

16-ch Current Input Module with Data Logger
M-7017mC-16-G
M-7017mC-16-G
M-7017mC-16-G
M-7017mC-16-G
M-7017mC-16-G
M-7017mC-16-G
M-7017mC-16-G
M-7017mC-16-G

Features

  • 16 Current Inputs
  • Built-in Resistor to Simplify Current Measurement
  • Jumper Selectable Differential or Single-ended Wiring
  • 16-bit Resolution
  • Adjustable Sampling Rate (Fast/Normal Mode)
  • Storage for up to 100,000 Records from16 Current Inputs
  • Built-in Dual Watchdog
CE UKCA FCC RoHS WEEE

Introduction

The M-7017mC-16 is a 16-channel current input module that is specifically designed to measure current only. Its user-friendly design saves both time and effort when measuring current thanks to built-in resistors, meaning that you can now measure current directly without adding an external resistor. The module also provides 4 kV ESD protection and 110 VDC overvoltage protection for the current input and features 3000 VDC intra-module isolation and open wire detection for 4 ~ 20 mA input.

The sampling rate of the M-7017mC-16 is adjustable, meaning that either fast mode or normal mode can be set. The module contains a data logger that can be used to record the current input from all 16 channels, including date and time stamps, and can store up to 100,000 downloadable records.

LogReader is a simple tool that can be used to read the log data of the module and then export it to a CSV file. The user can download it from the Download Center.


 

Applications


• Building Automation
• Factory Automation
• Machine Automation
• Remote Maintenance
• Remote Diagnosis
• Testing Equipment

Ordering Information

PRODUCT SERIES DESCRIPTION QNT. INQUIRY
PRODUCT SERIES M-7017mC-16-G     CR DESCRIPTION16-ch Current Input Module with Data Logger using DCON and Modbus Protocols (Gray Cover) (RoHS)
This combination include other products.

Similar Products

Data Logger
Max. Records Up to 100,000 records from 16 current input channels
CPU Module
Real Time Clock Yes
Watchdog Timer Module, Communication (Programmable)
Isolation
Intra-module Isolation 3000 VDC
EMS Protection
EFT (IEC 61000-4-4) ±4 kV for Power Line
ESD (IEC 61000-4-2) ±4 kV Contact for Each Terminal
Surge (IEC 61000-4-5) ±2 kV for Power Line
LED Indicators
Status 1 x Power and Communication
Analog Input
Channels 16 Differential or Single-ended Wiring (Jumper Selectable)
Range ±20 mA, 0 ~ 20 mA, 4 ~ 20 mA
Resolution 16-bit
Accuracy Normal Mode: ±0.1% of FSR
Fast Mode: ±0.2 % of FSR
Sampling Rate Normal Mode: 10 Hz
Fast Mode: 200 Hz
Common Voltage Protection 25 VDC
Overvoltage Protection 110 VDC
Overcurrent Protection 50 mA at 110 VDC
Individual Channel Configuration Yes
Open Wire Detection For 4 ~ 20 mA Only
COM Ports
Ports 1 x RS-485
Baud Rate 1200 ~ 115200 bps
Data Format (N, 8, 1), (N, 8, 2), (E, 8, 1), or (O, 8, 1)
Protocol Modbus RTU, DCON
Power
Reverse Polarity Protection Yes
Input Range +10 ~ +48 VDC
Consumption 0.6 W
Mechanical
Dimensions (mm) 76 x 121 x 42 (W x L x H)
Installation DIN-Rail Mounting
Environment
Operating Temperature -25 ~ +75 °C
Storage Temperature -40 ~ +85 °C
Humidity 10 ~ 95% RH, Non-condensing